Main circuit terminal specifications

1.3 Main circuit terminal specifications

1.3.1

Specification of main circuit terminal

Terminal
Terminal Name
Symbol
R/L1,
S/L2,
AC power input
T/L3
U, V, W
Inverter output
R1/L11,
Power supply for
S1/L21
control circuit
Brake unit
P/+, N/-
connection
DC reactor
P/+, P1
connection
PR, PX
Please do not remove or use terminals PR and PX or the jumper connected.
Earth
1.3.2
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring.
400V class
FR-F740-00023 to 00126-EC
Screw size (M4)
R/L1 S/L2 T/L3
Jumper
R1/L11 S1/L21
IM
Power
Motor
supply
6
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter
(FR-HC, MT-HC) or power regeneration common converter (FR-CV).
Connect a three-phase squirrel-cage motor.
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
alarm display and alarm output or when using the high power factor
converter (FR-HC, MT-HC) or power regeneration common converter (FR-
CV), remove the jumpers from terminals R/L1-R1/L11 and S/L2-S1/L21
and apply external power to these terminals.
Do not turn off the power supply for control circuit (R1/L11, S1/L21) with the
main circuit power (R/L1, S/L2, T/L3) on. Doing so may damage the
inverter. The circuit should be configured so that the main circuit power (R/
L1, S/L2, T/L3) is also turned off when the power supply for control circuit
(R1/L11, S1/L21) is off.
00380 or less : 60VA, 00470 or more : 80VA
Connect the brake unit (FR-BU, BU and MT-BU5), power regeneration
common converter (FR-CV), high power factor converter (FR-HC and
MT-HC) or power regeneration converter (MT-RC).
For the 01160 or less, remove the jumper across terminals P/+ - P1 and
connect the DC reactor. (For the 01800 or more, a DC reactor is
supplied as standard.)
For earthing the inverter chassis. Must be earthed.
Jumper
PR
N/-
P/+
PX
Screw size
Charge lamp
(M4)
Description
FR-F740-00170, 00250-EC
Jumper
R1/L11 S1/L21
Screw size
(M4)
R/L1 S/L2 T/L3
Power supply
Charge lamp
N/-
P/+ PR
Jumper
PX
IM
Motor
Screw size
(M4)