GE L90 Instruction Manual page 571

L90 line current differential system ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 17 of 57)
ADDR
REGISTER NAME
4488
...Repeated for CT Bank 3
448C
...Repeated for CT Bank 4
4490
...Repeated for CT Bank 5
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (3 modules)
4500
Phase VT 1 Connection
4501
Phase VT 1 Secondary
4502
Phase VT 1 Ratio
4504
Auxiliary VT 1 Connection
4505
Auxiliary VT 1 Secondary
4506
Auxiliary VT 1 Ratio
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
Source Settings (Read/Write Setting) (6 modules)
4580
Source 1 Name
4583
Source 1 Phase CT
4584
Source 1 Ground CT
4585
Source 1 Phase VT
4586
Source 1 Auxiliary VT
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
4601
Phase Rotation
4602
Frequency And Phase Reference
4603
Frequency Tracking Function
87L Power System (Read/Write Setting)
4610
Number of Terminals
4611
Number of Channels
4612
Charging Current Compensation
4613
Positive Sequence Reactance
4614
Zero Sequence Reactance
4615
Zero Sequence Current Removal
4616
Local Relay ID
4617
Terminal 1 ID
4618
Terminal 2 ID
4619
Channel Asymmetry Compensation
461A
Block GPS Time Reference
461B
Maximum Channel Asymmetry
461C
Round Trip Time
Breaker control (read/write settings)
4700
Breaker 1 function
4701
Breaker 1 name
4704
Breaker 1 mode
4705
Breaker 1 open
4706
Breaker 1 close
4707
Breaker 1 phase A / three-pole closed
4708
Breaker 1 phase B closed
4709
Breaker 1 phase C closed
470A
Breaker 1 external alarm
470B
Breaker 1 alarm delay
GE Multilin
RANGE
0 to 1
50 to 240
1 to 24000
0 to 6
50 to 240
1 to 24000
---
0 to 63
0 to 63
0 to 63
0 to 63
25 to 60
0 to 1
0 to 5
0 to 1
2 to 3
1 to 2
0 to 1
0.1 to 65.535
0.1 to 65.535
0 to 1
0 to 255
0 to 255
0 to 255
0 to 65535
0 to 65535
0 to 10
0 to 10
0 to 1
---
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1000000
L90 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F100
V
0.1
F001
:1
1
F060
---
1
F166
V
0.1
F001
:1
1
F060
---
---
F206
---
1
F400
---
1
F400
---
1
F400
---
1
F400
Hz
1
F001
---
1
F106
---
1
F167
---
1
F102
---
1
F001
---
1
F001
---
1
F102
kohms
0.001
F001
kohms
0.001
F001
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F300
---
1
F300
ms
0.1
F001
ms
0.1
F001
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F003
DEFAULT
B
0 (Wye)
664
1
1 (Vag)
664
1
"SRC 1"
0
0
0
0
60
0 (ABC)
0 (SRC 1)
1 (Enabled)
2
1
0 (Disabled)
100
100
0 (Disabled)
0
0
0
0
0
15
15
0 (Disabled)
"Bkr 1"
0 (3-Pole)
0
0
0
0
0
0
0
B-25

Advertisement

Table of Contents
loading