GE L90 Instruction Manual page 207

L90 line current differential system ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5 SETTINGS
SETTING
BREAKER 1 FUNCTION
= Enabled
= Disabled
SETTING
BREAKER 1 BLOCK OPEN
Off = 0
D60, L60, and L90 devices only from trip output
FLEXLOGIC OPERANDS
TRIP PHASE A
TRIP PHASE B
TRIP PHASE C
TRIP 3-POLE
SETTING
BREAKER 1 OPEN
Off = 0
61850 Select & Open
USER 3 OFF/ON
To open BRK1-(Name)
AND
SETTING
BREAKER 1 PUSHBUTTON
CONTROL
= Enabled
AND
USER 2 OFF/ON
To open BRK1-(Name)
SETTING
BREAKER 1 CLOSE
Off = 0
61850 Select & Close
C60, D60, L60, and L90 relays from recloser
FLEXLOGIC OPERAND
AR CLOSE BKR 1
SETTING
BREAKER 1 BLOCK CLOSE
Off = 0
Figure 5–17: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2)
IEC 61850 functionality is permitted when the L90 is in "Programmed" mode and not in the local control mode.
NOTE
GE Multilin
OR
OR
AND
SETTING
AND
MANUAL CLOSE RECAL1 TIME
0
OR
L90 Line Current Differential System
5.4 SYSTEM SETUP
FLEXLOGIC OPERANDS
BREAKER 1 OFF CMD
AND
BREAKER 1 TRIP A
BREAKER 1 TRIP B
AND
BREAKER 1 TRIP C
AND
AND
BKR ENABLED
OR
FLEXLOGIC OPERAND
AND
BREAKER 1 MNL CLS
FLEXLOGIC OPERAND
AND
BREAKER 1 ON CMD
827061AS.CDR
To breaker control
logic sheet 2,
842025A1
5
5-71