Flexcurves - GE L90 Instruction Manual

L90 line current differential system ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5.4 SYSTEM SETUP
a) SETTINGS
PATH: SETTINGS
SYSTEM SETUP
FLEXCURVE A
FlexCurves™ A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter a
custom FlexCurve™, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE UP/DOWN keys) for the desired protection curve (A, B, C, or D).
Table 5–5: FLEXCURVE™ TABLE
RESET
TIME
RESET
MS
0.00
0.05
0.10
0.15
0.20
5
0.25
0.30
0.35
0.40
0.45
0.48
0.50
0.52
0.54
0.56
0.58
0.60
0.62
0.64
0.66
The relay using a given FlexCurve™ applies linear approximation for times between the user-entered
points. Special care must be applied when setting the two points that are close to the multiple of pickup of
NOTE
1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin-
ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu.
5-76

FLEXCURVES

FLEXCURVE A TIME AT
0.00 xPKP:
TIME
OPERATE
MS
0.68
1.03
0.70
1.05
0.72
1.1
0.74
1.2
0.76
1.3
0.78
1.4
0.80
1.5
0.82
1.6
0.84
1.7
0.86
1.8
0.88
1.9
0.90
2.0
0.91
2.1
0.92
2.2
0.93
2.3
0.94
2.4
0.95
2.5
0.96
2.6
0.97
2.7
0.98
2.8
L90 Line Current Differential System
FLEXCURVE A(D)
Range: 0 to 65535 ms in steps of 1
0 ms
TIME
OPERATE
TIME
OPERATE
MS
MS
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
4.0
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
5 SETTINGS
5.4.7 FLEXCURVES™
TIME
OPERATE
MS
4.9
10.5
5.0
11.0
5.1
11.5
5.2
12.0
5.3
12.5
5.4
13.0
5.5
13.5
5.6
14.0
5.7
14.5
5.8
15.0
5.9
15.5
6.0
16.0
6.5
16.5
7.0
17.0
7.5
17.5
8.0
18.0
8.5
18.5
9.0
19.0
9.5
19.5
10.0
20.0
GE Multilin
TIME
MS

Advertisement

Table of Contents
loading

Table of Contents