5.4 SYSTEM SETUP
PATH: SETTINGS
SYSTEM SETUP
87L POWER SYSTEM
'
5
Any changes to the L90 power system settings will change the protection system configuration. As such,
the 87L protection at all L90 protection system terminals must be temporarily disabled to allow the relays
NOTE
to acknowledge the new settings.
NUMBER OF TERMINALS: This setting is the number of the terminals of the associated protected line.
NUMBER OF CHANNELS: This setting should correspond to the type of communications module installed. If the relay
is applied on two terminal lines with a single communications channel, this setting should be selected as "1". For a two
terminal line with a second redundant channel for increased dependability, or for three terminal line applications, this
setting should be selected as "2".
CHARGING CURRENT COMPENSATION: This setting enables and disables the charging current calculations and
corrections of current phasors. The voltage signals used for charging current compensation are taken from the source
assigned with the
assigned to this source. The following diagram shows possible configurations.
5-64
87L POWER SYSTEM
NUMBER OF TERMINALS:
2
NUMBER OF CHANNELS:
MESSAGE
1
CHARGING CURRENT
MESSAGE
COMPENSATN: Disabled
POS SEQ CAPACITIVE
MESSAGE
REACTANCE:
ZERO SEQ CAPACITIVE
MESSAGE
REACTANCE:
ZERO SEQ CURRENT
MESSAGE
REMOVAL: Disabled
LOCAL RELAY ID
MESSAGE
NUMBER: 0
TERMINAL 1 RELAY ID
MESSAGE
NUMBER: 0
TERMINAL 2 RELAY ID
MESSAGE
NUMBER: 0
CHNL ASYM COMP:
MESSAGE
Off
BLOCK GPS TIME REF:
MESSAGE
Off
MAX CHNL ASYMMETRY:
MESSAGE
1.5 ms
ROUND TRIP TIME
MESSAGE
CHANGE: 1.5 ms
CURRENT DIFF SIGNAL SOURCE 1
L90 Line Current Differential System
Range: 2, 3
Range: 1, 2
Range: Disabled, Enabled
Range: 0.100 to 65.535 k
0.100 kΩ
Range: 0.100 to 65.535 k
0.100 kΩ
Range: Disabled, Enabled
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.0 to 10.0 ms in steps of 0.1
Range: 0.0 to 10.0 ms in steps of 0.1