GE L90 Instruction Manual page 577

L90 line current differential system ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 23 of 57)
ADDR
REGISTER NAME
5D10
...Repeated for Ground Time Overcurrent 2
5D20
...Repeated for Ground Time Overcurrent 3
5D30
...Repeated for Ground Time Overcurrent 4
5D40
...Repeated for Ground Time Overcurrent 5
5D50
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5E00
Ground Instantaneous Overcurrent 1 Signal Source
5E01
Ground Instantaneous Overcurrent 1 Function
5E02
Ground Instantaneous Overcurrent 1 Pickup
5E03
Ground Instantaneous Overcurrent 1 Delay
5E04
Ground Instantaneous Overcurrent 1 Reset Delay
5E05
Ground Instantaneous Overcurrent 1 Block
5E06
Ground Instantaneous Overcurrent 1 Target
5E07
Ground Instantaneous Overcurrent 1 Events
5E08
Reserved (8 items)
5E10
...Repeated for Ground Instantaneous Overcurrent 2
5E20
...Repeated for Ground Instantaneous Overcurrent 3
5E30
...Repeated for Ground Instantaneous Overcurrent 4
5E40
...Repeated for Ground Instantaneous Overcurrent 5
5E50
...Repeated for Ground Instantaneous Overcurrent 6
5E60
...Repeated for Ground Instantaneous Overcurrent 7
5E70
...Repeated for Ground Instantaneous Overcurrent 8
5E80
...Repeated for Ground Instantaneous Overcurrent 9
5E90
...Repeated for Ground Instantaneous Overcurrent 10
5EA0
...Repeated for Ground Instantaneous Overcurrent 11
5EB0
...Repeated for Ground Instantaneous Overcurrent 12
L90 Trip Logic (Read/Write Grouped Setting)
5EE0
87L Trip Function
5EE1
87L Trip Source
5EE2
87L Trip Mode
5EE3
87L Trip Supervision
5EE4
87L Trip Force 3 Phase
5EE5
87L Trip Seal In
5EE6
87L Trip Seal In Pickup
5EE7
87L Trip Target
5EE8
87L Trip Events
Stub Bus (Read/Write Grouped Setting)
5F10
Stub Bus Function
5F11
Stub Bus Disconnect
5F12
Stub Bus Trigger
5F13
Stub Bus Target
5F14
Stub Bus Events
50DD Disturbance Detection (Read/Write Grouped Setting)
5F20
50DD Function
5F21
50DD Non Current Supervision
5F22
50DD Control Logic
5F23
50DD Logic Seal In
5F24
50DD Events
Setting Groups (Read/Write Setting)
5F80
Setting Group for Modbus Comms (0 means group 1)
5F81
Setting Groups Block
5F82
FlexLogic to Activate Groups 2 through 6 (5 items)
5F89
Setting Group Function
5F8A
Setting Group Events
GE Multilin
RANGE
0 to 5
0 to 1
0 to 30
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0 to 65535
0 to 65535
0 to 1
0.2 to 0.8
0 to 2
0 to 1
0 to 1
0 to 65535
---
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 5
0 to 65535
0 to 65535
0 to 1
0 to 1
L90 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F167
---
1
F102
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F157
---
1
F300
---
1
F300
---
1
F102
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
DEFAULT
B
0 (SRC 1)
0 (Disabled)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (3-Pole)
0
0
0 (Disabled)
20
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0
0 (Disabled)
0
0
0
0 (Disabled)
0 (Disabled)
B-31