5.6 GROUPED ELEMENTS
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
VOLTAGE ELEMENTS
5
These protection elements can be used for a variety of applications such as:
•
Undervoltage Protection: For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current which may cause dangerous overheating in the motor. The undervoltage protection feature can be used
to either cause a trip or generate an alarm when the voltage drops below a specified voltage setting for a specified time
delay.
•
Permissive Functions: The undervoltage feature may be used to block the functioning of external devices by operat-
ing an output relay when the voltage falls below the specified voltage setting. The undervoltage feature may also be
used to block the functioning of other elements through the block feature of those elements.
5-258
SETTING GROUP 1(6)
PHASE
UNDERVOLTAGE1
PHASE
MESSAGE
UNDERVOLTAGE2
PHASE
MESSAGE
UNDERVOLTAGE3
PHASE
MESSAGE
OVERVOLTAGE1
PHASE
MESSAGE
OVERVOLTAGE2
PHASE
MESSAGE
OVERVOLTAGE3
NEUTRAL OV1
MESSAGE
NEUTRAL OV2
MESSAGE
NEUTRAL OV3
MESSAGE
AUXILIARY UV1
MESSAGE
AUXILIARY UV2
MESSAGE
AUXILIARY UV3
MESSAGE
AUXILIARY OV1
MESSAGE
AUXILIARY OV2
MESSAGE
AUXILIARY OV3
MESSAGE
VOLTS/HZ 1
MESSAGE
VOLTS/HZ 2
MESSAGE
T60 Transformer Protection System
VOLTAGE ELEMENTS
See page 5–260.
See page 5–260.
See page 5–260.
See page 5–261.
See page 5–261.
See page 5–261.
See page 5–262.
See page 5–262.
See page 5–262.
See page 5–263.
See page 5–263.
See page 5–263.
See page 5–264.
See page 5–264.
See page 5–264.
See page 5–265.
See page 5–265.
5 SETTINGS
5.6.11 VOLTAGE ELEMENTS
GE Multilin