GE T60 Instruction Manual page 175

Ur series transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5 SETTINGS
5.2 PRODUCT SETUP
Example 3 — Incorrect
IP1/Mask1: 10.1.1.2/255.0.0.0
IP2/Mask2: 10.2.1.2/255.0.0.0
IP3/Mask3: 10.3.1.2/255.0.0.0
This example is incorrect because the mask of 255.0.0.0 used for the three IP addresses makes them belong to the same
network of 10.x.x.x.
Single LAN, No Redundancy
The topology shown in the following figure allows communications to SCADA, local configuration/monitoring through
EnerVista, and access to the public network shared on the same LAN. No redundancy is provided.
Figure 5–4: NETWORK CONFIGURATION FOR SINGLE LAN
Public Network
SCADA
EnerVista Software
5
LAN1
ML3000
P1
P2
P3
IP1/
MAC1
UR
859708A2.vsd
GE Multilin
T60 Transformer Protection System
5-29

Hide quick links:

Advertisement

Table of Contents
loading