5.8 INPUTS AND OUTPUTS
b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES
In a T60 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each
GOOSE message is programmed in the
GSSE/GOOSE CONFIGURATION
Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the
CONFIGURATION
TRANSMISSION
In T60 releases previous to 5.0x, these name strings were represented by the
c) REMOTE DEVICES: ID OF DEVICE FOR RECEIVING GSSE/GOOSE MESSAGES

PATH: SETTINGS
INPUTS/OUTPUTS
 REMOTE DEVICE
Remote devices are available for setting purposes. A receiving relay must be programmed to capture messages from only
those originating remote devices of interest. This setting is used to select specific remote devices by entering (bottom row)
the exact identification (ID) assigned to those devices.
5
The
REMOTE DEVICE 1 ETYPE APPID
sages. This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre-
sponding settings on the sending device.
The
REMOTE DEVICE 1 DATASET
DNA and UserSt bit pairs), or one of the configurable datasets.
Note that the dataset for the received data items must be made up of existing items in an existing logical node. For this rea-
son, logical node GGIO3 is instantiated to hold the incoming data items. GGIO3 is not necessary to make use of the
received data. The remote input data item mapping takes care of the mapping of the inputs to remote input FlexLogic oper-
ands. However, GGIO3 data can be read by IEC 61850 clients.

PATH: SETTINGS
INPUTS/OUTPUTS
 REMOTE INPUT 1
Remote Inputs that create FlexLogic operands at the receiving relay are extracted from GSSE/GOOSE messages originat-
ing in remote devices. Each remote input can be selected from a list consisting of: DNA-1 through DNA-32, UserSt-1
through UserSt-32, and Dataset Item 1 through Dataset Item 32. The function of DNA inputs is defined in the IEC 61850
5-318
SETTINGS

TRANSMISSION
FIXED GOOSE
SETTINGS
PRODUCT SETUP


GSSE
GSSE ID

REMOTE DEVICES
1
REMOTE DEVICE
Remote Device 1
REMOTE DEVICE
MESSAGE
ETYPE APPID: 0
REMOTE DEVICE
MESSAGE
DATASET: Fixed
setting is only used with GOOSE messages; they are not applicable to GSSE mes-
setting provides for the choice of the T60 fixed (DNA/UserSt) dataset (that is, containing


REMOTE INPUTS

REMOTE INPUT
Remote Ip
REMOTE IN
MESSAGE
Remote Device
REMOTE IN
MESSAGE
None
REMOTE IN
MESSAGE
STATE: Off
REMOTE IN
MESSAGE
EVENTS: Disabled
T60 Transformer Protection System

PRODUCT SETUP
COMMUNICATIONS

setting.
GOOSE ID


COMMUNICATIONS
setting.
RELAY NAME
REMOTE DEVICE 1(16)
Range: up to 20 alphanumeric characters
1 ID:
Range: 0 to 16383 in steps of 1
1
Range: Fixed, GOOSE 1 through GOOSE 16
1
REMOTE INPUT 1(32)
Range: up to 12 alphanumeric characters
1 ID:
1
Range: Remote Device 1 to Remote device 16
1 DEVICE:
1
Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32,
1 ITEM:
Config Item 1 to Config Item 32
Range: On, Off, Latest/On, Latest/Off
1 DEFAULT
Range: Disabled, Enabled
1
5 SETTINGS

IEC 61850 PROTOCOL
IEC 61850 PROTOCOL
GSSE/GOOSE
setting.