6.3 METERING
The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text is replaced by whatever name was programmed by the user for the associated source (see
SETUP
SIGNAL SOURCES
When VTs are configured in wye, the T60 calculates power in each phase and three-phase power is measured as
When VTs are configured in delta, the T60 does not calculate power in each phase and three-phase power is measured as
6
where
S is the apparent power
V
, V
, V
, I
, I
, I
are phase voltage and phase current phasors
A
B
C
A
B
C
V
and V
are phase-to-phase voltage phasors
AB
CB
Î is the conjugate of I
g) ENERGY METERING
PATH: ACTUAL VALUES
ENERGY
SRC 1
The metered values for real and reactive energy are displayed in this menu. The "SRC 1" text will be replaced by whatever
name was programmed by the user for the associated source (see
Because energy values are accumulated, these values should be recorded and then reset immediately prior to changing
CT or VT characteristics.
6-20
SRC 1
REACTIVE PWR
MESSAGE
φc:
0.000
SRC 1
APPARENT PWR
MESSAGE
3φ:
0.000
SRC 1
APPARENT PWR
MESSAGE
φa:
0.000
SRC 1
APPARENT PWR
MESSAGE
φb:
0.000
SRC 1
APPARENT PWR
MESSAGE
φc:
0.000
SRC 1
POWER FACTOR
MESSAGE
3φ:
SRC 1
POWER FACTOR
MESSAGE
φa:
SRC 1
POWER FACTOR
MESSAGE
φb:
SRC 1
POWER FACTOR
MESSAGE
φc:
).
S = V
x Î
A
S = V
METERING
SOURCE SRC 1
SRC 1
POS WATTHOUR:
0.000
SRC 1
NEG WATTHOUR:
MESSAGE
0.000
SRC 1
POS VARHOUR:
MESSAGE
0.000
SRC 1
NEG VARHOUR:
MESSAGE
0.000
T60 Transformer Protection System
var
VA
VA
VA
VA
1.000
1.000
1.000
1.000
+ V
x Î
+ V
x Î
A
B
B
C
C
x Î
+ V
x Î
AB
A
CB
C
ENERGY
Wh
Wh
varh
varh
SETTINGS
6 ACTUAL VALUES
SETTINGS
SYSTEM SETUP
SIGNAL SOURCES
GE Multilin
SYSTEM
(EQ 6.1)
(EQ 6.2)
).