5 SETTINGS
I
= protected element base (nominal) current
B
To ensure element accuracy for high overcurrent conditions, the maximum value of I/(k x I
istically it is exceeding this value.
The reset time of the thermal overload protection element is also time delayed using following formula:
In the above equation,
τ
= thermal protection trip time constant
rst
T
is a minimum reset time setting
min
Figure 5–156: IEC 255-8 SAMPLE OPERATE AND RESET CURVES
The thermal overload protection element estimates accumulated thermal energy E using the following equations calculated
each power cycle. When current is greater than the pickup level, I
GE Multilin
2
(
kI
)
B
τ
×
---------------------------- -
t
ln
=
+
rst
rst
2
2
(
)
I
kI
B
> k × I
n
T60 Transformer Protection System
5.7 CONTROL ELEMENTS
) is limited to 8, even when real-
B
T
min
, element starts increasing the thermal energy:
B
(EQ 5.52)
5
5-309