5 SETTINGS
c) PHASE OVERVOLTAGE (ANSI 59P, IEC PTOV)

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE
 OVERVOLTAGE1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
There are three phase overvoltage elements available. A phase overvoltage element is used as an instantaneous element
with no intentional time delay or as a definite time element. The input voltage is the phase-to-phase voltage, either mea-
sured directly from delta-connected VTs or as calculated from phase-to-ground (wye) connected VTs. The specific voltages
to be used for each phase are shown below.
If the source VT is wye-connected, then the phase overvoltage pickup condition is
and V
.
CA
NOTE
GE Multilin
SETTING GROUP 1(6)
PHASE OV1
FUNCTION: Disabled
PHASE OV1 SIGNAL
SOURCE: SRC 1
PHASE OV1
PICKUP: 1.000 pu
PHASE OV1 PICKUP
DELAY:
1.00 s
PHASE OV1 RESET
DELAY:
1.00 s
PHASE OV1 BLOCK:
Off
PHASE OV1
TARGET: Self-reset
PHASE OV1
EVENTS: Disabled
Figure 5–126: PHASE OVERVOLTAGE SCHEME LOGIC
T60 Transformer Protection System
5.6 GROUPED ELEMENTS


VOLTAGE ELEMENTS
PHASE OVERVOLTAGE1(3)
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic Operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
V
>
×
3
Pickup
for V
, V
,
AB
BC
5-261
5