5.9 TRANSDUCER INPUTS AND OUTPUTS
where: x is a driving signal specified by the
I
and I
min
max
k is a scaling constant calculated as:
The feature is intentionally inhibited if the
< 0.1 pu. The resulting characteristic is illustrated in the following figure.
VAL
5
The DCmA output settings are described below.
DCMA OUTPUT F1 SOURCE: This setting specifies an internal analog value to drive the analog output. Actual values
(FlexAnalog parameters) such as power, current amplitude, voltage amplitude, power factor, etc. can be configured as
sources driving DCmA outputs. Refer to Appendix A for a complete list of FlexAnalog parameters.
DCMA OUTPUT F1 RANGE: This setting allows selection of the output range. Each DCmA channel may be set inde-
pendently to work with different ranges. The three most commonly used output ranges are available.
DCMA OUTPUT F1 MIN VAL: This setting allows setting the minimum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current. The setting is entered
in per-unit values. The base units are defined in the same manner as the FlexElement base units.
DCMA OUTPUT F1 MAX VAL: This setting allows setting the maximum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current. The setting is entered
in per-unit values. The base units are defined in the same manner as the FlexElement base units.
The
DCMA OUTPUT F1 MIN VAL
the
DCMA OUTPUT F1 SOURCE
NOTE
Three application examples are described below.
EXAMPLE: POWER MONITORING
A three phase active power on a 13.8 kV system measured via UR-series relay source 1 is to be monitored by the DCmA
H1 output of the range of –1 to 1 mA. The following settings are applied on the relay: CT ratio = 1200:5, VT secondary 115,
VT connection is delta, and VT ratio = 120. The nominal current is 800 A primary and the nominal power factor is 0.90. The
power is to be monitored in both importing and exporting directions and allow for 20% overload compared to the nominal.
The nominal three-phase power is:
The three-phase power with 20% overload margin is:
5-336
SOURCE
are defined by the
setting
RANGE
------------------------------------------------ -
k
=
MAX VAL
MAX VAL
I
max
I
min
MIN VAL
Figure 5–169: DCMA OUTPUT CHARACTERISTIC
and
DCMA OUTPUT F1 MAX VAL
is set to FlexAnalog value based on power factor measurement).
×
P
3
13.8 kV 0.8 kA
=
×
P
1.2 17.21 MW
=
max
T60 Transformer Protection System
setting
I
I
max
min
MIN VAL
and
settings are entered incorrectly, e.g. when
MIN VAL
DRIVING SIGNAL
MAX VAL
settings are ignored for power factor base units (i.e. if
×
×
0.9
17.21 MW
=
20.65 MW
=
5 SETTINGS
MAX VAL
842739A1.CDR
(EQ 5.56)
MIN
(EQ 5.57)
(EQ 5.58)
GE Multilin