9.2 DIFFERENTIAL CHARACTERISTIC TEST EXAMPLES
Yg/D30° TRANSFORMER WITH PHASE B TO C FAULT ON THE DELTA SIDE.
Transformer: Y/D30°, 20 MVA, 115/12.47 kv, CT1 (200:1), CT2 (1000:1)
Figure 9–4: CURRENT DISTRIBUTION ON A YG/D30° TRANSFORMER WITH AN a TO b FAULT ON THE LV SIDE
Three adjustable currents are required in this case. The Phase A and C Wye-side line currents, identical in magnitude but
displaced by 180°, can be simulated with one current source passed through these relay terminals in series. The second
current source simulates the Phase B primary current. The third source simulates the delta "b" and "c" phase currents, also
equal in magnitude but displaced by 180°.
TEST
PHASE
Balanced
Condition
Min Pickup
change the
Min PKP to
0.2 pu
Minimum
Pickup
Slope 1
return the
Min PKP to
0.1 pu
Slope 1
Intermediate
Slope 1 & 2
Intermediate
9
Slope 1 & 2
Slope 2
9-10
I (f) = 0.5 pu –270°
A
A
I (f) = 1 pu –90°
B
B
C
I (f) = 0.5 pu –270°
C
INJECTED CURRENT
W1 CURRENT
W2 CURRENT
0.25 ∠0°
A
0.5 ∠–180°
0.8 ∠0°
B
C
0.25 ∠0°
0.8 ∠–180°
A
0.25 ∠0°
0.5 ∠–180°
0.95 ∠0°
B
0.25 ∠0°
0.95 ∠–180°
C
0.25 ∠0°
A
B
0.5 ∠–180°
1.05 ∠0°
C
0.25 ∠0°
1.05 ∠–180°
A
0.25 ∠0°
0.5 ∠–180°
0.92 ∠0°
B
0.25 ∠0°
0.92 ∠–180°
C
0.25 ∠0°
A
B
0.5 ∠–180°
0.95 ∠0°
C
0.25 ∠0°
0.95 ∠–180°
2 ∠0°
A
4 ∠–180°
B
2 ∠0°
1 ∠–180°
C
2 ∠0°
A
B
4 ∠–180°
0.8 ∠0°
C
2 ∠0°
0.8 ∠–180°
4 ∠0°
A
8 ∠–180°
0.8 ∠0°
B
4 ∠0°
0.8 ∠–180°
C
T60 Transformer Protection System
Y/d30° Transformer
DISPLAYED CURRENT
DIFFERENTIAL
0 ∠0°
0 ∠0°
0 ∠0°
0 ∠0°
0 ∠0°
0 ∠0°
0.154 ∠0°
0.155 ∠0°
0 ∠0°
0 ∠0°
0.253 ∠0°
0.255 ∠0°
0 ∠0°
0 ∠0°
0.123 ∠0°
0.123 ∠0°
0 ∠0°
0 ∠0°
0.153 ∠0°
0.153 ∠0°
0 ∠0°
0 ∠0°
1 ∠0°
5.37 ∠–180°
5.37 ∠0°
0 ∠0°
0 ∠0°
5.57 ∠–180°
5.57 ∠0°
0 ∠0°
0 ∠0°
11.93 ∠–180°
11.93 ∠0°
9 COMMISSIONING

9.2.4 TEST EXAMPLE 3

I (f) = 0
a
A
I (f) = 0.866 pu –90°
b
B
F
C
I (f) = 0.866 pu –270°
c
828738A1.CDR
STATUS
RESTRAINT
0 ∠0°
Not Applicable
0.8 ∠0°
0.8 ∠–180°
0 ∠0°
Block
I
= 0.051 < Min PKP
d
0.948 ∠0°
0.950 ∠–180°
0 ∠0°
Operate
I
= 0.102 > Min PKP
d
1.049 ∠0°
1.050 ∠–180°
0 ∠0°
Block
I
I
/
= 13.2%
d
r
0.919 ∠0°
0.919 ∠–180°
0 ∠0°
Operate
I
I
/
= 15.9%
d
r
0.948 ∠0°
0.948 ∠–180°
0 ∠0°
Block
I
I
/
= 84.3%
d
r
6.37 ∠0°
< 86.6%
computed
6.37 ∠–180°
0 ∠0°
Operate
I
I
/
= 87.5%
d
r
6.37 ∠0°
> 86.6%
computed
6.37 ∠–180°
0 ∠0°
Block
I
I
/
= 93.7%
d
r
12.73 ∠0°
< Slope 2 = 95%
12.73 ∠–180°