GE T60 Instruction Manual page 471

Ur series transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5 SETTINGS
Setting the
TELEPROT INPUT ~~ DEFAULT
defaults the input to logic 0 when the channel fails.
The "Latest/On" and "Latest/Off" values freeze the input in case of lost communications. If the latest state is not known,
such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for "Latest/On"
and logic 0 for "Latest/Off".
c) TELEPROTECTION OUTPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 TELEPROT OUTPUTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
As the following figure demonstrates, processing of the teleprotection inputs/outputs is dependent on the number of com-
munication channels and terminals. On two-terminal two-channel systems, they are processed continuously on each chan-
nel and mapped separately per channel. Therefore, to achieve redundancy, the user must assign the same operand on
both channels (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On
three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel
failure between any pair of relays.
GE Multilin
setting to "On" defaults the input to logic 1 when the channel fails. A value of "Off"


TELEPROTECTION
TELEPROT OUTPUTS
TELEPROT OUTPUT 1-1:
Off
TELEPROT OUTPUT 1-2:
Off
TELEPROT OUTPUT 1-16:
Off
TELEPROT OUTPUT 2-1:
Off
TELEPROT OUTPUT 2-2:
Off
TELEPROT OUTPUT 2-16:
Off
T60 Transformer Protection System
5.8 INPUTS AND OUTPUTS
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
5
5-325

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents