GE T60 Instruction Manual page 387

Ur series transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5 SETTINGS
NEUTRAL DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the
forward direction. When selecting this setting it must be kept in mind that the design uses a 'positive-sequence
restraint' technique for the "Calculated 3I0" mode of operation.
NEUTRAL DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the
reverse direction. When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint
technique for the "Calculated 3I0" mode of operation.
Figure 5–113: NEUTRAL DIRECTIONAL OVERCURRENT LOGIC
GE Multilin
T60 Transformer Protection System
5.6 GROUPED ELEMENTS
5-241
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents