5 SETTINGS
f) LOSS OF LIFE

PATH: SETTINGS
GROUPED ELEMENTS
 LOSS OF LIFE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The Loss of Life element detects the accumulated total consumed transformer life. This element can be set to issue an
alarm or trip when the actual accumulated transformer life becomes larger than the user-specified loss of life pickup value.
For new transformers installations, the
ers, the user should pre-determine the consumed transformer life in hours.
LOSS OF LIFE INITIAL VALUE: Enter a setting for the consumed transformer life in hours. When the Loss of Life ele-
ment is enabled, the computed loss of life will be added to the initial loss of life.
LOSS OF LIFE PICKUP: Enter the expended life, in hours, required for operation of the element. This setting should
be above the total transformer life set as a reference based on nominal loading conditions and a 30°C ambient temper-
ature, as outlined in the IEEE standards.
GE Multilin
Figure 5–103: AGING FACTOR LOGIC
SETTING GROUP 1(6)
TRANSFORMER
LOSS OF LIFE
FUNCTION: Disabled
LOSS OF LIFE INITIAL
VALUE: 0 hrs
LOSS OF LIFE PICKUP:
180000 hrs
LOSS OF LIFE BLOCK:
Off
LOSS OF LIFE TARGET:
Self-Reset
setting should be "0". For previously installed transform-
XFMR INITIAL LOSS OF LIFE
T60 Transformer Protection System
5.6 GROUPED ELEMENTS

LOSS OF LIFE
Range: Disabled, Enabled
Range: 0 to 500000 hrs. in steps of 1
Range: 0 to 500000 hrs. in steps of 1
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
5
5-221