Interoperability Document; D.1.3 Interoperability Document - GE T60 Instruction Manual

Ur series transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

D.1 IEC 60870-5-103
The boxes indicate the following:  – used in standard direction;  – not used.
1.
PHYSICAL LAYER
Electrical interface
 EIA RS-485
32 Number of loads for one protection equipment
Optical interface
 Glass fibre
 Plastic fibre
 F-SMA type connector
 BFOC/2.5 type connector
Transmission speed
 9600 bits/s
D
 19200 bits/s
2.
LINK LAYER
There are no choices for the link layer.
3.
APPLICATION LAYER
Transmission mode for application data
Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion stan-
dard.
Common address of ASDU
 One COMMON ADDRESS OF ASDU (identical with station address)
 More than one COMMON ADDRESS OF ASDU
Selection of standard information numbers in monitor direction
System functions in monitor direction
INF Semantics
 <0> End of general interrogation
 <0> Time synchronization
 <2> Reset FCB
 <3> Reset CU
 <4> Start/restart
 <5> Power on
Status indications in monitor direction
INF Semantics
 <16> Auto-recloser active
 <17> Teleprotection active
 <18> Protection active
 <19> LED reset
 <20> Monitor direction blocked
 <21> Test mode
D-2
T60 Transformer Protection System
APPENDIX D

D.1.3 INTEROPERABILITY DOCUMENT

GE Multilin