GE T60 Instruction Manual page 653

Ur series transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 49 of 73)
ADDR
REGISTER NAME
Breaker Restrike (Read/Write Setting) (3 modules)
9930
Breaker Restrike 1 Function
9931
Breaker Restrike 1 Block
9933
Breaker Restrike 1 Signal Source
9934
Breaker Restrike 1 Pickup
9935
Breaker Restrike 1 Reset Delay
9936
Breaker Restrike 1 HF Detect
9937
Breaker Restrike 1 Breaker Open
9939
Breaker Restrike 1 Open Command
993B
Breaker Restrike 1 Close Command
993D
Breaker Restrike 1 Target
993E
Breaker Restrike 1 Events
993F
Reserved (2 items)
9941
...Repeated for Breaker Restrike 2
9952
...Repeated for Breaker Restrike 3
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9980
Teleprotection Clear Lost Packets
Teleprotection Inputs/Outputs (Read/Write Settings)
9990
Teleprotection Function
9991
Teleprotection Number of Terminals
9992
Teleprotection Number of Channels
9993
Teleprotection Local Relay ID
9994
Teleprotection Terminal 1 ID
9995
Teleprotection Terminal 2 ID
9996
Reserved (10 items)
9A00
Teleprotection Input 1-n Default States (16 items)
9A10
Teleprotection Input 2-n Default States (16 items)
9A20
Teleprotection Output 1-n Operand (16 items)
9A40
Teleprotection Output 2-n Operand (16 items)
Teleprotection Channel Tests (Read Only)
9AA0
Teleprotection Channel 1 Status
9AA1
Teleprotection Channel 1 Number of Lost Packets
9AA2
Teleprotection Channel 2 Status
9AA3
Teleprotection Channel 2 Number of Lost Packets
9AA4
Teleprotection Network Status
9AAF
Teleprotection Channel 1 Input States
9AB0
Teleprotection Channel 2 Input States
9AC0
Teleprotection Input 1 States, 1 per register (16 items)
9AD0
Teleprotection Input 2 States, 1 per register (16 items)
VT Fuse Failure (Read/Write Setting) (6 modules)
A09A
VT Fuse Failure1 Function
A09B
VT Fuse Failure Neutral Wire Open1 Function
A09C
VT Fuse Failure Neutral Wire Open 1 3rd Harmonic Pickup
A09D
...Repeated for module number 2
A0A0
...Repeated for module number 3
A0A3
...Repeated for module number 4
A0A6
...Repeated for module number 5
A0A9
...Repeated for module number 6
VT Fuse Failure Actuals (Read Only) (6 modules)
A0AC
VT Fuse Failure 1 V0 3rd Harmonic
A0AE
...Repeated for module number 2
A0B0
...Repeated for module number 3
A0B2
...Repeated for module number 4
A0B4
...Repeated for module number 5
GE Multilin
RANGE
0 to 1
0 to 4294967295
0 to 5
0.10 to 2.00
0 to 65.535
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
---
0 to 1
0 to 1
2 to 3
1 to 2
0 to 255
0 to 255
0 to 255
0 to 1
0 to 3
0 to 3
0 to 4294967295
0 to 4294967295
0 to 2
0 to 65535
0 to 2
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 3
0 to 999999.999
T60 Transformer Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F300
---
1
F167
pu
0.01
F001
s
0.001
F001
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
---
F002
---
1
F126
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F086
---
1
F086
---
1
F300
---
1
F300
---
1
F134
---
1
F001
---
1
F134
---
1
F001
---
1
F134
---
1
F500
---
1
F500
---
1
F108
---
1
F108
---
1
F102
---
1
F102
pu
0.001
F001
V
0.001
F060
DEFAULT
0 (Disabled)
0
0 (SRC 1)
50
B
100
1 (Enabled)
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (No)
0 (Disabled)
2
1
0
0
0
0
0 (Off)
0 (Off)
0
0
1 (OK)
0
2 (n/a)
0
2 (n/a)
0
0
0 (Off)
0 (Off)
0 (Disabled)
0 (Disabled)
100
0