4.5.2 IAC-B with a 4–Breaker Dual Feed Configuration (MBP, MIS, BIB and RIB)............45 4.5.3 UPS to IAC-B Breaker Wiring......................... 48 4.6 Initial Startup ............................51 4.7 Completing the Installation Checklist ......................51 Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 4
9 9 W W a a r r r r a a n n t t y y ............................................................7 7 1 1 9.1 Warranty..............................71 Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 5
Cabinet Ventilation – Top Venting ....................17 Figure 10. Eaton 93PM-L 160/200kW IAC-B as Shipped on Pallet ................. 24 Figure 11. Removing the Pallet Skids and Supports – Eaton 93PM-L IAC-B ............. 26 Figure 12. 93PM-L IAC-B Interface Terminal Location ..................29 Figure 13.
Page 6
List of Figures Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 7
UPS External Power Cable Terminations .................... 21 Table 6. Supplied External Wiring Terminal Hardware Kit ................... 22 Table 7. Recommended Installation Parts and Tools (Not Supplied by Eaton) ............22 Table 8. IAC-B All Interface Wiring Terminal Block Terminations ................. 32 Table 9.
Page 8
List of Tables viii Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
160/200 kW (208V) Series Uninterruptible Power Supplies (UPSs). The IAC-B provides maintenance bypass functions with configurable features, enabling adaptation and expansion without costly electrical rework. The 93PM-L IAC-B is available in 160 kW or 200 kW rated versions, in either 2–Breaker, 3–Breaker or 4–Breaker configurations.
M M o o d d e e l l C C o o n n f f i i g g u u r r a a t t i i o o n n s s The following model configurations are available: • Eaton 93PM-L 160kW IAC-B (208V) and Eaton 93PM-L 200kW IAC-B (208V) Sliding Interlock plate or Trapped Key Interlock in the following configurations: –...
Using This Manual Figure 4. Eaton 93PM-L IAC-B (Right-side install) with Eaton 93PM-L UPS 93PM-L 160/200 kW UPS (208V) 93PM-L IAC-B 1 1 . . 5 5 U U s s i i n n g g T T h h i i s s M M a a n n u u a a l l This manual describes how to install the IAC-B and is divided into chapters.
Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01 Eaton, Powerware, and BladeUPS are registered trademarks of Eaton Corporation or its subsidiaries and affiliates. Eaton, Powerware, and BladeUPS are registered trademarks of Eaton Corporation or its subsidiaries and affiliates.
F F o o r r M M o o r r e e I I n n f f o o r r m m a a t t i i o o n n Refer to the Eaton 93PM-L UPS 20–160 kW (208V) Installation and Operation Manual or the Eaton 93PM-L UPS 20–200 kW (208V) Installation and Operation Manual for the following additional information:...
1 1 . . 1 1 0 0 E E q q u u i i p p m m e e n n t t R R e e g g i i s s t t r r a a t t i i o o n n Please visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory. Model Number: Serial Number:...
Page 17
Ensure all power is disconnected before performing installation or service. • ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS system or battery wiring or connectors. Attempting to alter wiring may result in serious injury or death. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
The operating environment should be maintained within the parameters stated in this manual. • Keep surroundings uncluttered, clean, and free from excess moisture. • Observe all DANGER, WARNING, and CAUTION notices affixed to the inside and outside of the equipment. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Service Engineer, or the warranty terms specified in Chapter 9 Warranty become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Page 20
4 Breakers, Dual Feed Input 510 (1125) 452 (996) 4 at 113 (249) NOTE Shipping weight does not include the weight of the line-and-match wiring. Line-and-Match wiring is shipped on a separate pallet. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 21
None Required From Right Side of Cabinet None Required None Required From Left Side of Cabinet NOTE *Additional Top of Cabinet clearance may be required for conduit in top entry applications. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Preparing the Site Figure 5. 93PM-L IAC-B Cabinet Dimensions (Front, Right Side, and Back Views) Side View Front View Back View 1067 (Top Venting Option) [42.0] [31.3] 1880 [74.0] [1.9] [1.5] [4.0] [2.3] [11.2] [15.3] [20.1] [24.8] [24.8] [27.3] [37.8] Dimensions are in millimeters [inches] Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
451 [995] 4 Breakers, Dual Feed Input 932.6 [36.7] 557.1 [21.9] 396.8 [15.6] 460 [1015] NOTE Weights do not include wiring between the UPS and the IAC-B or customer provided wiring. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Top View (Rear Venting Option) (Rear Venting Option) Cover Ventilation Plate Grill Figure 9. Cabinet Ventilation – Top Venting Back View Top View (Top Venting Option) (Top Venting Option) Ventilation Grill Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 26
Use twisted-pair wires for each input and return or common. • Eaton provides interface wiring between the UPS and the IAC-B for MBP, MIS Aux contact and the BIB shunt trip. All other interface wiring and conduit is to be supplied by the customer.
Page 27
UPS and the maintenance bypass. • Refer to the appropriate Eaton 93PM-L UPS installation and operation manual listed in paragraph 1.8 For More Information for UPS cabinet conduit and terminal specifications and locations.
Page 28
Minimum Conductor Size (Phase A, B, and C) Number per Phase (each) Conduit Size Inches Number (each) Neutral Wire Size AWG or kcmil 300 MCM Number (each) Minimum Conductor Size (Ground) AWG or kcmil Number (each) Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 30
500 MCM Manual Hydraulic Crimp Tool 14 Ton Die Set NOTE For additional information (including part numbers and manufacturer information) and/or assistance contact an Eaton service representative (see paragraph 1.9 Getting Help). Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Carefully inspect the outer packaging for evidence of damage during transit. CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE...
Inspecting and Unpacking the IAC-B Figure 10. Eaton 93PM-L 160/200kW IAC-B as Shipped on Pallet Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 33
11. Place a floor protector from the parts kit underneath each jacking bolt, and screw the bolts down against them. The floor protectors protect the floor from being marred by the jacking bolts. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Unloading the IAC-B from the Pallet Figure 11. Removing the Pallet Skids and Supports – Eaton 93PM-L IAC-B Rear Cabinet Support Right Side Cabinet Support Cabinet Mounting Bolts (4 places front) (4 places rear) (4 places left side) Cabinet (4 places right side)
Page 35
24. Using the cabinet mounting bolts from the kit, install the floor mounting brackets to the front and rear of the IAC-B with the angle facing outward. 25. Secure the cabinet to the floor with customer-supplied hardware. 26. Proceed to paragraph 4.5 Installing IAC-B External Power Wiring. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
To install wiring: Verify the UPS system is turned off and all power sources are removed. NOTE Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual listed in paragraph 1.8 For More Information, for detailed information on UPS operating procedures, wiring access, terminal locations, termination recommendations and building alarm terminal assignments.
Figure 13. Interface Wiring Location Wire Tie Anchors Interface Wiring Area NOTE: Wire tie anchors are located on both the left and right sides and along the top back panel of the cabinet. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
3 BIB AUX NC IND RELAY AUX NC 5 BIB SHUNT TRIP + IND RELAY AUX COM 6 BIB SHUNT TRIP - 8 RIB AUX NO 9 RIB AUX COM 10 RIB AUX NC Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 40
NOTE UPS building alarm signals are customer programmable. Customer interface wiring for the IAC-B MBP assumes that the UPS Building Alarm is programmed to monitor Normally Open (NO) contacts. Review the IAC-B Terminal Block 1 Wiring Diagram, see Figure Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 41
Verify the UPS system is turned off and all power sources are removed. NOTE Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual listed in paragraph 1.8 For More Information, for detailed information on UPS operating procedures, wiring access, terminal locations, termination recommendations and building alarm terminal assignments.
BIB interface wiring is installed using the inter-cabinet wiring access pass-through. Verify the UPS system is turned off and all power sources are removed. NOTE Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual listed in paragraph 1.8 For More Information...
Page 43
Verify the UPS system is turned off and all power sources are removed. NOTE Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual listed in paragraph 1.8 For More Information, for detailed information on UPS operating procedures, wiring access, terminal locations, termination recommendations and building alarm terminal assignments.
Page 44
Table 10 for the IAC-B wiring information and terminal assignments. NOTE Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual listed in paragraph 1.8 For More Information for detailed information on the UPS interface terminal location and terminal assignments.
Page 45
Installing the IAC-B Interface Connections NOTE Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual listed in paragraph 1.8 For More Information for detailed information on UPS operating procedures, wiring access, terminal locations, termination recommendations and building alarm terminal assignments.
Figure 16. Typical Bus Bar Barrel Lug Mounting – Hardware Assembly Sequence Bolt Head Conical Washer Flat Washer Bus Bar Threaded Clinch Nut Single Lug Installation Bolt Head Conical Washer Flat Washer Bus Bar Threaded Clinch Nut Double Lug Installation Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
1.8 For More Information, for UPS installation procedures. Verify the UPS system is turned off and all power sources are removed. Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual, listed in paragraph 1.8 For More Information, for UPS operating procedures.
Figure 17. Line-Up-and-Match Wiring Access Locations Inter-cabinet wiring access to route interface wiring between cabinets. Inter-cabinet wiring access knockouts. Remove knockouts as required to route power wiring between cabinets. Left Side View Right Side View Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
IAC-B wiring and termination recommendations. Route the maintenance ground and bypass neutral wire through the top of the IAC-B to the ground and neutral terminals in the lower cabinet area. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
(E12) power wiring from the IAC-B output terminals (E9, E10, and E11) in the lower cabinet area to the critical load. 18. Continue to paragraph 4.5.3 UPS to IAC-B Breaker Wiring. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Figure 21. IAC-B Lower Cabinet Terminal Detail Output Neutral Phase A (Top) AC Output Phase B To Critical Bypass Neutral Load (Bottom) Phase C Ground Lugs Neutral Disconnect Lower Cabinet Area View of IAC-B Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 53
IAC-B and the UPS output, and between the IAC-B and the critical load. Pull the wiring through the conduit into the wiring area. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
Page 54
(E12) power wiring from the IAC-B output terminals (E9, E10 and E11) in the lower cabinet area to the critical load. 24. Continue to paragraph 4.5.3 UPS to IAC-B Breaker Wiring. Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
3.2.3 IAC-B Power Wiring Preparation, Table 5 for IAC-B wiring and termination recommendations. Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual, listed in paragraph 1.8 For More Information, for the UPS terminal locations and termination recommendations. Route the Output Ground cable from the UPS cabinet through the wiring access pass-through to the ground terminals in the lower cabinet area.
Page 57
15. Reinstall all safety shield panels previously removed and secure with the retained hardware. 16. Close the outside door and secure the latch. 17. After the IAC-B is installed and wired, return to the applicable Eaton 93PM-L UPS Installation and Operation manual, listed in paragraph 1.8 For More...
9.1 Warranty become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date. 4 4 . . 7 7 C C o o m m p p l l e e t t i i n n g g t t h h e e I I n n s s t t a a l l l l a a t t i i o o n n C C h h e e c c k k l l i i s s t t The final step in installing the IAC-B is completing the following Installation Checklist.
* Dashed lines indicate optional components. E9, E10, E11, E12 AC Output to Maintenance Tie Bus MIS Breaker 208 V Isolation E9, E10, E11, E12 Breaker (MIS) AC Output to Load 208 V Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
6 = BIB Shunt Trip - 7 = Not Used 8 = RIB Aux NO 9 = RIB Aux Common 10 = RIB Aux NC BLACK BLUE BIB Shunt Trip WHITE YELLOW BLACK BLUE Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
5 = Ind Relay Aux NC 6 = Ind Relay Aux Common 7 = Not Used 8 = Not Used 9 = Not Used INDUSTRIAL RELAY CARD 10 = Not Used OF UPS TB 3 Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
BIB (if installed) CLOSED RIB (if installed) CLOSED Start the UPS. Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual, listed in paragraph 1.8 For More Information, for UPS operating procedures. Close the door and secure the latch.
32). Open the MIS. The critical load is supplied by the maintenance bypass source. Shut down the UPS. Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual, listed in paragraph 1.8 For More Information, for UPS operating procedures.
Page 69
If installed, close the BIB. If installed, close the RIB. Start the UPS in bypass mode. Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual, listed in paragraph 1.8 For More Information, for UPS operating procedures.
11. Insert key “A” into the solenoid lock and lock. The critical load is supplied by the maintenance bypass source. 12. Shut down the UPS. Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual, listed in paragraph 1.8 For More Information, for UPS operating procedures.
Page 72
10. Insert key “A” into the solenoid lock and lock. 11. Close the front door and secure the latch. 12. Transfer the UPS to Normal mode. Refer to the applicable Eaton 93PM-L UPS Installation and Operation manual, listed in paragraph 1.8 For More...
7 7 . . 2 2 . . 3 3 A A N N N N U U A A L L M M a a i i n n t t e e n n a a n n c c e e Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings.
M M a a i i n n t t e e n n a a n n c c e e T T r r a a i i n n i i n n g g A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance.
5 to 40°C (41 to 104°F). The recommended operating temperature is 25°C (77° Operating Temperature Storage Temperature -25 to +55°C (-13 to +131°F) Operating Altitude Maximum 1500m (5000 ft) at 40°C without derating Eaton 93PM-L IAC-B Installation and Operation Manual P-164000764—Rev 01...
For Product installed (and currently located) outside the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (not including the costs of labor coverage). The defective Warranted Item will be refurbished or replaced onsite at the End-User's location or such other location as determined by Eaton.
Page 80
Eaton shall not be responsible for failure to provide service or parts due to causes beyond Eaton's reasonable control. In no case will Eaton's liability under this Warranty exceed the replacement value of the Warranted Items.