Page 3
5.10 Third Party Intellectual Property Rights. The Firmware may contain components transfer the Firmware directly to a third party only in connection with the sale of the Eaton (including open source software components) that are owned by third parties (“Third Party product in which it is installed.
5 5 O O n n e e l l i i n n e e s s a a n n d d S S c c h h e e m m a a t t i i c c s s ..................................................5 5 7 7 5.1 Power Onelines ............................57 5.2 Interface Onelines ............................ 60 5.3 Schematics ............................. 61 Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 6
8 8 W W a a r r r r a a n n t t y y ............................................................6 6 7 7 Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 7
Figure 7. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW as Shipped on Pallet ............27 Figure 8. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW Battery Breaker Location – Front View with Front Door Removed ........................... 28 Figure 9. Removing the Pallet Skids and Supports – Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW ......31 Figure 10.
Page 8
List of Figures viii Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
In addition, the IBC-LHW provides a single battery cabinet solution for Eaton 93PM and 93PM-L UPS systems 200 kW and below. Eaton 93PM 400 kW UPS systems above 200 kW require at least two battery cabinets.
UPS cabinet as viewed from the front of the cabinet. See Figure 2 for line-up-and-match configuration view. Figure 2. Typical Eaton 93PM UPS and Two Eaton 93PM Universal Integrated Battery Cabinets Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Available B37, E28, E39, E54, N54, or H41 batteries. – Up to four IBC-LWs can be paralleled to extend the run time. Use with a Eaton 93PM-L 20-120 kW (208V) UPS. Use with a Eaton 93PM 20-50 kW UPS, Eaton 93PM 20-100 kW UPS, Eaton 93PM 20- 150 kW UPS, or Eaton 93PM 20-200 kW UPS.
(WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. recycling/reuse or hazardous waste center. recycling/reuse or hazardous waste center. recycling/reuse or hazardous waste center. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 16
E E q q u u i i p p m m e e n n t t R R e e g g i i s s t t r r a a t t i i o o n n Please visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory. Model Number: Serial Number: Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 17
Attempting to alter wiring can cause injury. • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 18
Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts–circuits de haute intensité. Prendre les précautions nécessaires. • Pour le replacement, utiliser le même nombre et modéle des batteries. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 19
Ne pas fumer près des accumulateurs. Ne pas produire de flamme ou d’étincelle dans la zone de l’accumulateur. Dissiper l'électricité statique de votre corps en touchant une surface reliée à la terre avant de toucher les accumulateurs. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 21
C C h h a a p p t t e e r r 3 3 I I n n s s t t a a l l l l a a t t i i o o n n P P l l a a n n a a n n d d U U n n p p a a c c k k i i n n g g Use the following basic sequence of steps to install the Eaton 93PM Universal Integrated Battery Cabinet- Large (IBC-LW) or Universal Integrated Battery Cabinet-Large High Rate (IBC-LHW): Create an installation plan for the IBC.
Page 22
25°C (77°F). Operating temperatures above the recommended range will result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton's Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more information.
Page 23
2205 (4861) 6 at 368 (810) Rate with E54 Batteries Universal Integrated Battery Cabinet-Large High 1947 (4293) 1902 (4193) 6 at 317 (699) Rate with B37 Batteries Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 24
Failure to recharge the batteries before the expiration of the shelf life will result in reduced discharge time, shorter float service life, and will void the warranty. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Installation Plan and Unpacking Figure 3. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW Dimensions (Front and Right Side Views) Dimensions are in millimeters [inches] Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Installation Plan and Unpacking Figure 4. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW Dimensions (Rear Views) Dimensions are in millimeters [inches] NOTE The IBC Front Floor Mounting Bracket’s mounting dimensions are identical to the Rear Floor Mounting Bracket dimensions. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Installation Plan and Unpacking Figure 5. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW Dimensions (Top and Bottom Views) Top View Bottom View Dimensions are in millimeters [inches] Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Installation Plan and Unpacking Figure 6. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW Center of Gravity Dimensions are in millimeters [inches] Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 29
Refer to national and local electrical codes for acceptable external wiring practices. • Material and labor for external wiring requirements are to be provided by the customer. • For external wiring, use 75°C copper wire. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 30
Table Table 8, or Table 9. Wire sizes listed are for copper wiring only. Table 6. Line-Up-and-Match External Power Wiring Recommendations – Eaton 93PM IBC-LW and Eaton 93PM IBC-LHW Battery Cabinet to UPS Recommended Conductor Number of Number per Pole...
Page 31
Installation Plan and Unpacking Table 7. Standalone External Power Wiring Recommendation – Eaton 93PM IBC-LW (300A Breaker) Battery Cabinet to UPS or External Customer Supplied Tie Point and Tie Point and Breaker Breaker or Disconnect or Disconnect to UPS Num-...
Page 32
Installation Plan and Unpacking Table 7. Standalone External Power Wiring Recommendation – Eaton 93PM IBC-LW (300A Breaker) (Continued) Battery Cabinet to UPS or External Customer Supplied Tie Point and Tie Point and Breaker Breaker or Disconnect or Disconnect to UPS...
Page 33
Installation Plan and Unpacking Table 8. Standalone External Power Wiring Recommendations – Eaton 93PM IBC-LW (400A Breaker) (Continued) Battery Cabinet to UPS or External Customer Supplied Tie Point and Tie Point and Breaker Breaker or Disconnect or Disconnect to UPS...
Page 34
Figure 14 Figure 16 show the location of the IBC power cable terminals. Table 10. External Power Cable Terminations – Eaton 93PM IBC-LW and Eaton 93PM IBC-LHW Screw Size Tightening Torque Terminal Func- Number and Size of...
Page 35
Installation Plan and Unpacking Table 10. External Power Cable Terminations – Eaton 93PM IBC-LW and Eaton 93PM IBC-LHW (Continued) Screw Size Tightening Torque Terminal Func- Number and Size of and Type Nm (lb in) Model Function Terminal tion Pressure Termination Battery –...
Page 36
Installation Plan and Unpacking • Because of the battery shunt trip wiring route in the Eaton 93PM UPS cabinet, the wiring from the IBC to the UPS must use wire rated for 600V and Class 1 wiring methods. • The battery detect signal wiring from the battery cabinet must be connected to a programmed UPS building alarm.
Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact an Eaton service representative immediately to determine the extent of the damage and its impact on further installation.
Installation Plan and Unpacking Figure 8. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW Battery Breaker Location – Front View with Front Door Removed Battery Breaker Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 39
Insert the forklift or pallet jack forks between the supports on the bottom of the pallet (see Figure 6 for the IBC cabinet center of gravity measurements). Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 40
Pull the two pallet skids out from under the left, right, front, rear, and two center supports. Recycle the pallet skids, supports, and hardware in a responsible manner. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Installation Figure 9. Removing the Pallet Skids and Supports – Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW Front Door Mounting Bolts (4 places top) (2 places bottom) Front Door Rear Support Right Support Jacking Bolts (2 places front) Skid Mounting Bolts...
Page 42
20; otherwise, proceed to Step 22. Install additional IBCs on the right or left side of the first IBC. 22. Proceed to paragraph 4.3 Installing IBC Power Wiring. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Inter-cabinet wiring access to route interface wiring between cabinets. Left Side View Right Side View Inter-cabinet wiring access knockouts. Remove knockouts as required to route power wiring between cabinets. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 45
Use this procedure to wire line-up-and-match Eaton 93PM Universal Integrated Battery Cabinets to the Eaton 93PM UPS cabinet. To install wiring to connections: Verify the UPS system is turned off and all power sources are removed. Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7 For More Information, for UPS operating procedures.
For a detailed view of the IBC terminal block, see Figure Connect the ground, positive, and negative DC power wiring from the battery cabinet or disconnect to the UPS cabinet ground and battery terminals. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 47
Installation Route the other end of the battery wiring (positive, negative, and ground) to the UPS cabinet external battery ground and input terminals. Refer to the applicable Eaton 93PM UPS Installation and Operation manual listed in paragraph 1.7 For More Information, for UPS cabinet terminal locations and termination requirements.
Installation Figure 16. DC Power Terminal Detail – Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW IBC DC (–) Output to UPS Negative Terminals (–) * IBC DC (+) Output to UPS Positive Terminals (+) * Ground Terminals * Terminal blocks are shipped uninstalled allowing the customer to point toward the top or bottom conduit landing as preferred.
Page 51
Use this procedure to wire standalone Eaton 93PM Universal Integrated Battery Cabinets to the Eaton 93PM UPS cabinet. To install wiring to connections: Verify the UPS system is turned off and all power sources are removed. Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7 For More Information, for UPS operating procedures.
Installation Figure 18. Battery Breaker Mount Screw Location and Mount Lever Location - Eaton 93PM IBC Battery Breaker Mount Screw Location Battery Breaker Mount Lever Location Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
For a detailed view of the DC power terminal shield, see Figure Figure 19. DC Power Terminal Shield Cut Lines for Top Entry Wiring 19. Reinstall the DC power terminal shield removed in Step Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Setting; otherwise, skip to paragraph 4.4 Battery Breaker Instantaneous Trip Setting. NOTE Internal battery strings are to be connected by an authorized Eaton Customer Service Engineer at system startup. Figure 20. IBC Bottom Entry Conduit and Wire Entry Locations Bottom Entry Conduit Landing (Remove plate to drill or punch conduit holes.)
Failure to adhere to 5x instantaneous trip setting voids the battery warranty. To verify the trip setting: Verify the UPS system is not in reserve mode or operating on battery. Refer to the applicable Eaton 93PM UPS installation and operation manual, listed in paragraph 1.7 For More Information, for UPS operating procedures.
12, and Figure 24 for wiring and termination requirements. NOTE 4 Refer to the applicable Eaton 93PM UPS Installation and Operation manual listed in paragraph 1.7 For More Information, for UPS cabinet terminal locations. To install wiring: If wiring the IBC battery detect interface terminals using line-up-and-match wiring using the inter-cabinet...
Page 58
Figure 10. Connect the battery detect interface wiring to the UPS battery detect interface (building alarm) terminals. Refer to the applicable Eaton 93PM UPS Installation and Operation manual listed in paragraph 1.7 For More Information, for UPS cabinet termination requirements.
Installation Figure 23. Interface Terminal Locations – Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW Interface Terminal Location Table 12. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW – TB2 Interface Connections Description Terminal TB2 Name Thermal Sensor (Optional) Contacts used to signal a battery temperature out of specification and to turn off the battery charger to prevent thermal runaway.
Installation Table 13. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW – TB2 Interface Wiring Terminal Block Terminations Tightening Torque Nm (lb Size of Pressure Type Terminal Function Termination Screw Comments Shunt Trip #26–#16 0.4 (3.5) - 0.8 (7.1) Slotted Use twisted-pair wires for each input and return or common.
Page 62
Disconnect terminal block plug from terminal block to wire plug. NOTE 2 Because of the battery shunt trip wiring route in the Eaton 93PM UPS cabinet, the wiring from the IBC shunt trip terminals to the UPS must use wire rated for 600V and Class 1 wiring methods.
Page 63
(see Figure 13. Once the battery cabinets are installed and wired, return to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7 For More...
Page 64
Figure 15. Once the battery cabinets are installed and wired, return to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7 For More Information, to complete the UPS wiring.
Make a copy of the Installation Checklist before filling it out, and retain the original. After the installation is complete, an Eaton Customer Service Engineer must verify the operation of the UPS system and commission it to support the critical load. The service representative cannot perform any installation tasks other than verifying software and operating setup parameters.
Battery Cabinet 2 Battery Cabinet 3 Battery Cabinet 4 Four Battery Cabinets Maximum NOTE Battery cabinet wiring assumes using factory supplied wiring and one wire per pole. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Onelines and Schematics Figure 27. Eaton 93PM IBC-LW Standalone Power Online – One or Two Cabinets Internal Internal Battery Battery Breaker Breaker UPS Cabinet Battery Cabinet 1 Battery Cabinet 2 NOTE External wiring to be supplied by the customer. Figure 28. Eaton 93PM IBC-LW Standalone Power Online – Four Cabinets...
I I n n t t e e r r f f a a c c e e O O n n e e l l i i n n e e s s Figure 32 shows the UPS and 93PM IBC-LW or 93PM IBC-LHW intercabinet interface connection onelines. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
S S c c h h e e m m a a t t i i c c s s Figure 33 shows the Eaton 93PM IBC-LW and Eaton 93PM IBC-LHW schematic. Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
6 6 . . 2 2 . . 3 3 A A N N N N U U A A L L M M a a i i n n t t e e n n a a n n c c e e Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings.
Page 74
Phillips and Pozidriv are registered trademarks of Phillips Screw Company. A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system Copyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
M M o o d d e e l l N N u u m m b b e e r r s s The Universal Integrated Battery Cabinet (IBC) is available in two model to meet the needs of the Eaton 93PM UPS product line.
Page 76
Relative Humidity (operating and 95%, noncondensing storage) Acoustical Noise Not applicable Safety Conformance UL1778 5 edition Agency Markings cULus EMC (Class A) FCC Part 15 Class A and 62040-2 c3 Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04...
Page 77
C C h h a a p p t t e e r r 8 8 W W a a r r r r a a n n t t y y For warranty information, please refer to the Resources link on our website, www.eaton.com/93PM.
Need help?
Do you have a question about the 93PM IBC-LW and is the answer not in the manual?
Questions and answers