Environmental And Installation Considerations - Eaton 93PS-8(20)-20(-C) User And Installation Manual

93ps 8–40 kw
Table of Contents

Advertisement

Eaton 93PS UPS 8–40 kW
operating environment must meet the height, clearance, and environmental
requirements specified.
4.3.1
The UPS system installation requires a TN, TT or IT power distribution system
(the IT distribution system shall include a neutral wire).
The UPS system installation must meet the following guidelines:
The system must be installed on a level floor suitable for computer or
electronic equipment. The floor must be suitable for heavy weight and
wheeling.
The system must be installed in a temperature and humidity controlled
indoor area that is free of conductive contaminants.
The cabinet can be installed in line-up-and-match or standalone
configurations.
Failure to follow these guidelines may void your warranty.
Do not stack anything on top of the 93PS UPS cabinet.
Do not stack the UPS 93PS C-model cabinet on top of any other similar
cabinet(s).
If installed on a shelf, use suitable supports to prevent the UPS from tipping
or dropping.
The UPS equipment operating environment must meet the weight requirements
shown in Table
Table 4: Dimensions
Shipping dimen-
sions (WxDxH)
Cabinet dimensions
(WxDxH)
Table 5: UPS cabinet weights with cardboard packaging
Shipping weight
Installed weight
©
Eaton Corporation plc 2016. All rights reserved.

Environmental and installation considerations

5
, and the size requirements shown in Table
20 kW frame
[mm]
540 x 857 x 1,460
335 x 750 x 1,300
20 kW
frame
293 kg
280 kg
CAUTION
20 kW frame
C-model
[mm]
540 x 857 x 705
335 x 750 x 645
20 kW C-model
frame
98 kg
86 kg
Revision: 003
Document ID: P-164000493
User's and installation guide
4
.
40 kW frame
[mm]
750 x 820 x 1,975
480 x 750 x 1,750
40 kW
frame
558 kg
532 kg
35 (104)