Minislot Interface Connections; Installing Signal Interface Connections In A Parallel System - Eaton 93PS-8(20)-20(-C) User And Installation Manual

93ps 8–40 kw
Table of Contents

Advertisement

Eaton 93PS UPS 8–40 kW
Figure 17. Industrial Relay Card INDRELAY-MS
5.5.5
For MiniSlot accessories and communication devices selection, see Chapter
For installation and setup of a MiniSlot card, please contact your Eaton
representative.
To install wiring to the connections:
1.
If not already installed, install the LAN drops.
2.
Open the front door of the UPS.
3.
To remove the MiniSlot cover plate, remove the 2 screws securing the
plate.
4.
To install the MiniSlot communication device, push it all the way in.
5.
Secure the MiniSlot communication device with 2 screws.
6.
Route and install the LAN and other cables to the appropriate MiniSlot
cards. The cable route is through the signal cable canal in the top section
of the UPS.
7.
For operator instructions, refer to the manual supplied with the MiniSlot
card.
8.
When all the wiring is completed, close the front door and secure it with the
latch.
5.5.6
The installation of the signal interface connections in a parallel system is done
by following the aforementioned instructions. Signal inputs can be paralleled
between the units, that is, the same contact can be used for several units' signal
input signaling. This concerns also the EPO signal.
©
Eaton Corporation plc 2016. All rights reserved.

MiniSlot interface connections

Installing signal interface connections in a parallel system

Revision: 003
Document ID: P-164000493
User's and installation guide