EMC Capabilities
52.3.5
Immunity on DC Input/Output Power Ports
Table 170
Basic standard
Test level
Performance
Limit standard
Test level
Performance
Table 171
Limit standard
Test level
Performance
Table 172
Limit standard
Test level
Performance
52.3.6
Immunity on Telecommunication and External Signal Lines
Table 173
Basic standard
Test level
Performance
Limit standard
Test level
Performance
408 (485)
Fast transient test
EN 61000-4-4
2 kV common mode between all lines and cabinet ground reference
Criteria B for a complete system
ETS 300 342-2
2 kV common mode between all lines and cabinet ground reference
Criteria A for a complete system
Criteria TT for transmitter units
Criteria TR for receiver units
Surge test
ETS 300 342-2
1 kV common mode between line and cabinet ground reference
0.5 kV differential mode, between line and line
Criteria A for a complete system
Criteria TT for transmitter units
Criteria TR for receiver units
RF common mode test
ETS 300 342-2
3 V(rms)
Criteria A for a complete system
Criteria CT for transmitter units
Criteria CR for receiver units
Fast transient test
EN 61000-4-4
2 kV common mode between line and cabinet ground reference
Criteria B
ETS 300 342-2
4 kV common mode between line and cabinet ground reference
Criteria A for a complete system
Criteria TT for transmitter units
Criteria TR for receiver units