6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL
Positioning speed
Actual deceleration time
Set deceleration time
[2] Types of stop processes
The operation can be stopped with deceleration stop, sudden stop or immediate
stop.
(1) Deceleration stop
The operation stops with "deceleration time 0 to 3" (
Pr.30
).
Which time from "deceleration time 0 to 3" to use for control is set in positioning
Da.4
data (
).
(2) Sudden stop
The operation stops with "
(3) Servo OFF or free run (The operation stops with dynamic brake or
electromagnetic brake.)
The operation does not decelerate.
The QD75 immediately stops the command, but the operation will coast for the
droop pulses accumulated in the servo amplifier deviation counter.
Positioning speed
Actual sudden stop
deceleration time
Pr. 36 Sudden stop
deceleration time
Fig. 6.15 Types of stop processes
REMARK
1 "Deceleration stop" and "sudden stop" are selected with the details parameter 2
"stop group 1 to 3 sudden stop selection". (The default setting is "deceleration
stop".)
1
Pr.36
Sudden stop deceleration time".
6 - 71
MELSEC-Q
Pr.10
Pr.28
,
Positioning speed
Coast for the droop pulses accumulated
in the servo amplifier deviation counter.
Pr.29
,
,