GE L90 Instruction Manual page 234

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5.4 SYSTEM SETUP
b) BASIC CONFIGURATION
PATH: SETTINGS
PRODUCT SETUP
PMU 1 BASIC
CONFIGURATION
5
5-88
SYSTEM SETUP
PMU 1
FUNCTION: Disabled
PMU 1 ID CODE:
MESSAGE
1
PMU 1 STN:
MESSAGE
GE-UR-PMU
PMU 1 SIGNAL SOURCE:
MESSAGE
SRC 1
PMU 1 CLASS:
MESSAGE
Class M
PMU 1 FORMAT:
MESSAGE
Integer
PMU 1 STYLE:
MESSAGE
Polar
PMU 1 RATE:
MESSAGE
10
PMU 1 PHS-1:
MESSAGE
Va
PMU 1 PHS-1
MESSAGE
NM: GE-UR-PMU-PHS-1
PMU 1 PHS-14:
MESSAGE
Va
PMU 1 PHS-14:
MESSAGE
NM: GE-UR-PMU-PHS-14
PMU 1 A-CH-1:
MESSAGE
Off
PMU 1 A-CH-1:
MESSAGE
NM: AnalogChannel1
PMU 1 A-CH-16 (16):
MESSAGE
Off
PMU 1 A-CH-16 (16):
MESSAGE
NM: AnalogChannel16
PMU 1 D-CH-1:
MESSAGE
Off
PMU 1 D-CH-1
MESSAGE
NM: DigChannel1
PMU 1 D-CH-1
MESSAGE
NORMAL STATE: Off
L90 Line Current Differential System
PHASOR MEASUREMENT
BASIC CONFIGURATION
Range: Enabled, Disabled
Default: Disabled
Range: 1 to 65534 in steps of 1
Default: 1
Range: 16 -character ASCII string
Default: GE-UR-PMU
Range: Available signal sources
Default: SRC 1
Range: None, Class M, Class P
Default: Class M
Range: Integer, Floating Point
Default: Integer
Range: Polar, Rectangular
Default: Polar
Range: 1, 2, 4, 5, 10, 12, 15, 20, 25, 30, 50, 60, 100, 120
Default: 10
Range: Available synchrophasor values
Default: Va
Range: 16 -character ASCII string
Default: GE-UR-PMU-PHS-1
Range: Available synchrophasor values
Default: Va
Range: 16 -character ASCII string
Default: GE-UR-PMU-PHS-14
Range: Available FlexAnalog values
Default: Off
Range: 16 -character ASCII string
Default: AnalogChannel1
Range: Available FlexAnalog values
Default: Off
Range: 16 -character ASCII string
Default: AnalogChannel16
Range: Available FlexLogic™ operands
Default: Off
Range: 16 character ASCII string
Default: DigChannel1
Range: Off, On
Default: Off
5 SETTINGS
PMU1
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents