Advertisement

5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
TRANSMISSION
MESSAGE
MESSAGE
MESSAGE
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
GENERAL
GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
GSEE
GSSE
MESSAGE
MESSAGE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
GSSE ID
string identifies the GSSE message to the receiving device. In L90 releases previous to 5.0x, this name string was repre-
sented by the
setting.
RELAY NAME
GE Multilin
COMMUNICATIONS
IEC 61850 PROTOCOL
GENERAL
GSSE
FIXED GOOSE
CONFIGURABLE
GOOSE
COMMUNICATIONS
IEC 61850 PROTOCOL
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
sets the time between GSSE or GOOSE messages when there are no remote out-
setting is applicable to GSSE, fixed L90 GOOSE, and configurable GOOSE.
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE FUNCTION:
Enabled
GSSE ID:
GSSEOut
DESTINATION MAC:
000000000000
L90 Line Current Differential System
5.2 PRODUCT SETUP
GSSE/GOOSE CONFIGURATION
GSSE/GOOSE CONFIGURATION
Range: 1 to 60 s in steps of 1
GSSE/GOOSE CONFIGURATION
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address
5
5-23