GE L90 Instruction Manual page 187

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5 SETTINGS
If a number of protection elements are ORed to create a fault report trigger, the first operation of any element causing the
OR gate output to become high triggers a fault report. However, If other elements operate during the fault and the first oper-
ated element has not been reset (the OR gate output is still high), the fault report is not triggered again. Considering the
reset time of protection elements, there is very little chance that fault report can be triggered twice in this manner. As the
fault report must capture a usable amount of pre and post-fault data, it can not be triggered faster than every 20 ms.
Each fault report is stored as a file; the relay capacity is fifteen (15) files. An sixteenth (16th) trigger overwrites the oldest
file.
The EnerVista UR Setup software is required to view all captured data. The relay faceplate display can be used to view the
date and time of trigger, the fault type, the distance location of the fault, and the reclose shot number.
The
FAULT REPORT 1 SOURCE
breaker applications where the line current is supplied individually from two breaker CTs, the fault locator source should
include the sum of currents from both CTs as well as the line voltage.
The
setting assigns the FlexLogic™ operand representing the protection element/elements requiring
FAULT 1 REPORT TRIG
operational fault location calculations. The distance to fault calculations are initiated by this signal. The
and
MAG
FAULT REPORT 1 Z0 MAG
For a two-terminal line application, the
and
REPORT 1 Z0 ANG
FAULT REPORT 1 LENGTH
For a three-terminal application, these settings are used to enter the line segment impedance and length from the local ter-
minal to the tap point only.
The
FAULT REP 1 REM1-TAP Z1 MAG
enter positive sequence section impedances (in secondary ohms) for the line segment from remote terminal 1 to the tap
point. The length of the line section from remote terminal 1 to the tap point is entered in the
setting.
The
FAULT REP 1 REM2-TAP Z1 MAG
above, but for the line segment from remote terminal 2 to the tap point.
The
FAULT REPORT 1 VT SUBSTITUTION
nected VTs are used, and the relay is supplied with the neutral (3V0) voltage, this setting shall be set to "V0". The method is
still exact, as the fault locator would combine the line-to-line voltage measurements with the neutral voltage measurement
to re-create the line-to-ground voltages. See the
details. It required to configure the delta and neutral voltages under the source indicated as input for the fault report. Also,
the relay will check if the auxiliary signal configured is marked as "Vn" by the user (under VT setup), and inhibit the fault
location if the auxiliary signal is labeled differently.
If the broken-delta neutral voltage is not available to the relay, an approximation is possible by assuming the missing zero-
sequence voltage to be an inverted voltage drop produced by the zero-sequence current and the user-specified equivalent
zero-sequence system impedance behind the relay: V0 = –Z0
setting shall be set to "I0".
REPORT 1 VT SUBSTITUTION
The
FAULT REP 1 SYSTEM Z0 MAG
ting value is "I0". The magnitude is to be entered in secondary ohms. This impedance is an average system equivalent
behind the relay. It can be calculated as zero-sequence Thevenin impedance at the local bus with the protected line/feeder
disconnected. The method is accurate only if this setting matches perfectly the actual system impedance during the fault. If
the system exhibits too much variability, this approach is questionable and the fault location results for single-line-to-ground
faults shall be trusted with accordingly. It should be kept in mind that grounding points in vicinity of the installation impact
the system zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, etc.).
For proper operation of the multi-ended fault locator, the nominal primary voltage is expected to appear identical at
all line terminals as seen from the nominal secondary voltage, VT ratio, and VT connection settings of the first 87L
source.
NOTE
GE Multilin
setting selects the source for input currents and voltages and disturbance detection. For dual-
impedances are entered in secondary ohms.
FAULT REPORT 1 Z1 MAG
settings for the entire line must to be entered for fault location calculations.
and
FAULT REP 1 REM1-TAP Z1 ANG
,
FAULT REP 1 REM2-TAP Z1 ANG
setting shall be set to "None" if the relay is fed from wye-connected VTs. If delta-con-
ACTUAL VALUES
and
FAULT REP 1 SYSTEM Z0 ANGLE
L90 Line Current Differential System
,
,
FAULT REPORT 1 Z1 ANG
FAULT REPORT 1 Z0 MAG
settings are used for three-terminal applications to
FAULT REP 1 REM1-TAP LENGTH
, and
FAULT REP 1 REM2-TAP LENGTH
RECORDS
FAULT REPORTS
I0. In order to enable this mode of operation, the
settings are used only when the
5.2 PRODUCT SETUP
FAULT REPORT 1 Z1
,
FAULT
5
settings are used as
menu for additional
FAULT
set-
VT SUBSTITUTION
5-41

Advertisement

Table of Contents
loading

Table of Contents