5.10 TESTING
PATH: SETTINGS
TESTING

CHANNEL TESTS

This function performs checking of the communications established by both relays.
LOCAL LOOPBACK
REMOTE LOOPBACK
Refer to the Commissioning chapter for a detailed description of using the channel tests.
5
PATH: SETTINGS
TESTING
PMU 1
TEST VALUES
5-306
CHANNEL TESTS
LOCAL LOOPBACK
REMOTE LOOPBACK
MESSAGE
LOCAL LOOPBACK
FUNCTION: No
LOCAL LOOPBACK
MESSAGE
CHANNEL NUMBER: 1
REMOTE LOOPBACK
FUNCTION: No
REMOTE LOOPBACK
MESSAGE
CHANNEL NUMBER: 1
PMU TEST VALUES
PMU 1 TEST
FUNCTION: Disabled
PMU 1 VA TEST
MESSAGE
MAGNITUDE: 500.00 kV
PMU 1 VA TEST
MESSAGE
ANGLE: 0.00°
PMU 1 VB TEST
MESSAGE
MAGNITUDE: 500.00 kV
PMU 1 VB TEST
MESSAGE
ANGLE: –120.00°
PMU 1 VC TEST
MESSAGE
MAGNITUDE: 500.00 kV
PMU 1 VC TEST
MESSAGE
ANGLE: 120.00°
PMU 1 VX TEST
MESSAGE
MAGNITUDE: 500.00 kV
PMU 1 VX TEST
MESSAGE
ANGLE: 0.00°
PMU 1 IA TEST
MESSAGE
MAGNITUDE: 1.000 kA
PMU 1 IA TEST
MESSAGE
ANGLE: –10.00°
L90 Line Current Differential System
Range: Yes, No
Range: 1, 2
Range: Yes, No
Range: 1, 2
5.10.5 PHASOR MEASUREMENT UNIT TEST VALUES
PMU 1 TEST VALUES
Range: Enabled, Disabled
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
5 SETTINGS
5.10.4 CHANNEL TESTS