9 THEORY OF OPERATION
For two-terminal applications, the following equalities hold for the above equation.
For two-terminal applications, the distance is reported from the local relay. In three-terminal applications, the distance is
reported from the terminal of a given line segment.
Phase rotation must be the same at all line terminals for correct operation of the multi-ended fault locator.
NOTE
b) EXAMPLE
Consider a three-terminal, 500 kV application with no charging current compensation or zero-sequence removal. The
phase rotation is ABC and the following CT and VT data is known.
Table 9–1: CT AND VT APPLICATION DATA FOR MULTI-ENDED EXAMPLE
VALUE
RELAY 1
CT primary
1200 A
CT secondary
5 A
VT connection
wye
VT secondary
57.73 V
VT ratio
5000:1
The tap settings are shown below.
Table 9–2: TAP SETTINGS MULTI-ENDED EXAMPLE
VALUE
CT tap 1 for remote terminal 1
CT tap 1 for remote terminal 2
The primary positive-sequence impedances and length for the line are shown below.
Table 9–3: LINE LENGTH AND POSITIVE-SEQUENCE IMPEDANCE FOR MULTI-ENDED EXAMPLE
VALUE
Impedance
Length
The three relays are connected as shown below.
GE Multilin
V
V
1 X
TAP X
--------------------------------------- -
Z
---------------------------------------------------------------- -
D
Re
pu
I
FLT X
D
D
L
units
pu
V
V
1 X
LOC X
V
V
TAP X
REM1 X
I
I
TAP X
REM1 X
I
I
FLT X
LOC X
RELAY 2
1000 A
1 A
delta
83.33 V
6000:1
RELAY 1
RELAY 2
1000 / 1200 = 0.8333
1200 / 1000 = 1.200
1600 / 1200 = 1.3333
1600 / 1000 = 1.600
RELAY 1 TO TAP
RELAY 2 TO TAP
21.29
80.5°
36.50
70 km
120 km
L90 Line Current Differential System
I
TAP X
I
REM1 X
RELAY 3
1600 A
5 A
wye
57.73 V
5000:1
RELAY 3
1200 / 1600 = 0.750
1000 / 1600 = 0.625
RELAY 3 TO TAP
80.5°
16.73
80.5°
55 km
9.4 FAULT LOCATOR
(EQ 9.49)
(EQ 9.50)
9
9-27