User-Programmable Pushbuttons - GE L90 Instruction Manual

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
USER PUSHBUTTON 1
5
The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter-
ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered
with the relay.
Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons.
Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.
The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic™ oper-
ands) into FlexLogic™ equations, protection elements, and control elements. Typical applications include breaker control,
autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of
password protection.
The user-configurable pushbuttons for the enhanced faceplate are shown below.
5-52

USER-PROGRAMMABLE PUSHBUTTONS

PUSHBUTTON 1
FUNCTION: Disabled
PUSHBTN 1 ID TEXT:
MESSAGE
PUSHBTN 1 ON TEXT:
MESSAGE
PUSHBTN 1 OFF TEXT:
MESSAGE
PUSHBTN 1 HOLD:
MESSAGE
0.0 s
PUSHBTN 1 SET:
MESSAGE
Off
PUSHBTN 1 RESET:
MESSAGE
Off
PUSHBTN 1 AUTORST:
MESSAGE
Disabled
PUSHBTN 1 AUTORST
MESSAGE
DELAY: 1.0 s
PUSHBTN 1 REMOTE:
MESSAGE
Off
PUSHBTN 1 LOCAL:
MESSAGE
Off
PUSHBTN 1 DROP-OUT
MESSAGE
TIME: 0.00 s
PUSHBTN 1 LED CTL:
MESSAGE
Off
PUSHBTN 1 MESSAGE:
MESSAGE
Disabled
PUSHBUTTON 1
MESSAGE
EVENTS: Disabled
L90 Line Current Differential System
5.2.14 USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1(16)
Range: Self-Reset, Latched, Disabled
Range: Up to 20 alphanumeric characters
Range: Up to 20 alphanumeric characters
Range: Up to 20 alphanumeric characters
Range: 0.0 to 10.0 s in steps of 0.1
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Disabled, Enabled
Range: 0.2 to 600.0 s in steps of 0.1
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0 to 60.00 s in steps of 0.05
Range: FlexLogic™ operand
Range: Disabled, Normal, High Priority
Range: Disabled, Enabled
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents