GE L90 Instruction Manual page 602

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 24 of 59)
ADDR
REGISTER NAME
5EE4
87L Trip Force 3 Phase
5EE5
87L Trip Seal In
5EE6
87L Trip Seal In Pickup
5EE7
87L Trip Target
5EE8
87L Trip Events
B
Stub Bus (Read/Write Grouped Setting)
5F10
Stub Bus Function
5F11
Stub Bus Disconnect
5F12
Stub Bus Trigger
5F13
Stub Bus Target
5F14
Stub Bus Events
50DD Disturbance Detection (Read/Write Grouped Setting)
5F20
50DD Function
5F21
50DD Non Current Supervision
5F22
50DD Control Logic
5F23
50DD Logic Seal In
5F24
50DD Events
Setting Groups (Read/Write Setting)
5F80
Setting Group for Modbus Comms (0 means group 1)
5F81
Setting Groups Block
5F82
FlexLogic to Activate Groups 2 through 6 (5 items)
5F89
Setting Group Function
5F8A
Setting Group Events
Setting Groups (Read Only)
5F8B
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Current Differential 87L (Read/Write Grouped Setting)
6000
87L Current Differential Function
6001
87L Current Differential Block
6002
87L Current Differential Signal Source 1
6003
87L Minimum Phase Current Sensitivity
6004
87L Current Differential Tap Setting
6005
87L Current Differential Phase Percent Restraint 1
6006
87L Current Differential Phase Percent Restraint 2
6007
87L Current Differential Phase Dual Slope Breakpoint
6008
87L Current Differential Ground Function
6009
87L Current Differential Ground Pickup
600A
87L Current Differential Ground Restraint
600B
87L Current Differential Ground Delay
600C
87L Current Differential Key DTT
600D
87L Current Differential External Key DTT
600E
87L Current Differential Target
600F
87L Current Differential Event
6010
87L Current Differential Tap 2 Setting
6011
87L Current Differential Signal Source 2
6012
87L Current Differential Signal Source 3
6014
87L Current Differential Signal Source 4
B-32
RANGE
0 to 65535
0 to 1
0.2 to 0.8
0 to 2
0 to 1
0 to 1
0 to 65535
---
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 5
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
0 to 1
0 to 65535
0 to 5
0.1 to 4
0.2 to 5
1 to 50
1 to 70
0 to 20
0 to 1
0.05 to 1
1 to 50
0 to 5
0 to 1
0 to 65535
0 to 2
0 to 1
0.2 to 5
0 to 6
0 to 6
0 to 6
L90 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F300
---
1
F102
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
1
F102
---
1
F300
---
1
F167
pu
0.01
F001
---
0.01
F001
%
1
F001
%
1
F001
pu
0.1
F001
---
1
F102
pu
0.01
F001
%
1
F001
seconds
0.01
F001
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
0.01
F001
---
1
F211
---
1
F211
---
1
F211
DEFAULT
0
0 (Disabled)
20
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0
0 (Disabled)
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
0 (Disabled)
0
0 (SRC 1)
20
100
30
50
10
0 (Disabled)
10
25
10
1 (Enabled)
0
0 (Self-reset)
0 (Disabled)
100
0 (None)
0 (None)
0 (None)
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents