GE L90 Instruction Manual page 618

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 40 of 59)
ADDR
REGISTER NAME
90B4
...Repeated for FlexElement™ 10
90C8
...Repeated for FlexElement™ 11
90DC
...Repeated for FlexElement™ 12
90F0
...Repeated for FlexElement™ 13
9104
...Repeated for FlexElement™ 14
B
9118
...Repeated for FlexElement™ 15
912C
...Repeated for FlexElement™ 16
Fault Report Settings (Read/Write Setting) (up to 5 modules)
9200
Fault Report 1 Source
9201
Fault Report 1 Trigger
9202
Fault Report 1 Z1 Magnitude
9203
Fault Report 1 Z1 Angle
9204
Fault Report 1 Z0 Magnitude
9205
Fault Report 1 Z0 Angle
9206
Fault Report 1 Line Length Units
9207
Fault Report 1 Line Length
9208
Fault Report 1 VT Substitution
9208
Fault Report 1 System Z0 Magnitude
9208
Fault Report 1 System Z0 Angle
920B
...Repeated for Fault Report 2
9216
...Repeated for Fault Report 3
9221
...Repeated for Fault Report 4
922C
...Repeated for Fault Report 5
dcmA Outputs (Read/Write Setting) (24 modules)
9300
dcmA Output 1 Source
9301
dcmA Output 1 Range
9302
dcmA Output 1 Minimum
9304
dcmA Output 1 Maximum
9306
...Repeated for dcmA Output 2
930C
...Repeated for dcmA Output 3
9312
...Repeated for dcmA Output 4
9318
...Repeated for dcmA Output 5
931E
...Repeated for dcmA Output 6
9324
...Repeated for dcmA Output 7
932A
...Repeated for dcmA Output 8
9330
...Repeated for dcmA Output 9
9336
...Repeated for dcmA Output 10
933C
...Repeated for dcmA Output 11
9342
...Repeated for dcmA Output 12
9348
...Repeated for dcmA Output 13
934E
...Repeated for dcmA Output 14
9354
...Repeated for dcmA Output 15
935A
...Repeated for dcmA Output 16
9360
...Repeated for dcmA Output 17
9366
...Repeated for dcmA Output 18
936C
...Repeated for dcmA Output 19
9372
...Repeated for dcmA Output 20
9378
...Repeated for dcmA Output 21
937E
...Repeated for dcmA Output 22
9384
...Repeated for dcmA Output 23
938A
...Repeated for dcmA Output 24
IEC 61850 received integers (read/write setting registers)
9910
IEC61850 GOOSE UInteger 1 default value
9912
IEC61850 GOOSE UInteger input 1 mode
B-48
RANGE
0 to 5
0 to 65535
0.01 to 250
25 to 90
0.01 to 650
25 to 90
0 to 1
0 to 2000
0 to 2
0.01 to 650.00
25 to 90
0 to 65535
0 to 2
–90 to 90
–90 to 90
0 to 429496295
0 to 1
L90 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F167
---
1
F300
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
---
1
F147
0.1
F001
---
1
F270
ohms
0.01
F001
degrees
1
F001
---
1
F600
---
1
F522
pu
0.001
F004
pu
0.001
F004
---
1
F003
---
1
F491
DEFAULT
0 (SRC 1)
0
300
75
900
75
0 (km)
1000
0 (None)
900
75
0
0 (–1 to 1 mA)
0
1000
1000
0 (Default Value)
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents