5.13.5 Activating evac controls

Building Technologies
Fire Safety
1. Select 'Main menu' > 'Functions'.
 The 'Functions' window is open.
2. Select 'Activate / Deactivate'.
 A list of all element categories on which a command of the 'Activate /
Deactivate' command group can be executed is indicated.
3. Select the 'Evac control group' element category.
 The 'Enter address' window is open.
4. Press <ok> without entering an address.
 A list with all 'Evac controls' is open if more than one Evac category has
been configured.
5. Select an 'Evac control group' and press <softkey 1>.
 The 'Select command' window is open.
6. Select 'Activate/EVAC'.
 'Evac control' is activated.
 The window with the command response is open.
Example for the activation of 'Evac control'
Functions
Exit with <C>
On / Off
Test
Activate / Deactivate
Information
Function
On/Off
Select 'Activate / Deactivate' menu item, continue with <ok>
κ
Selecting element category
Area
Zone
Sounder
Evac control group
↑ Fire control group
Select 'Evac control group' element category, continue with <ok>
κ
Enter address
Evac gr --------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Continue with <ok> without entering an address
κ
Activation / Deactivation / Reset
(1)
(2)
(3)
(4)
Function
All
(1)
(2)
(3)
(4)
(5)
Operation
5
Access level 3
Configuration
(5)
Maintenance
(6)
All functions
(7)
LED
test
87 | 184
A6V10211076_i_en_--
2015-12-15