System description
9
Topology
9.2.3 Control tree
136 | 184
Building Technologies
Fire Safety
'Zone': Reset behavior of the manual call points
●
The reset behavior of an activated manual call point can be selected:
–
'ALARM' can always be reset; 'Glass broken' is indicated.
or
–
'ALARM' cannot be reset.
●
↑ Blocking of the isolation
–
If the isolation blocking function has been configured, the 'Zone' cannot be
switched off.
●
'Detector test' timeout
–
After the expiry of a configurable delay the system automatically cancels
the 'Detector test' state. This function can be deactivated.
●
Switching devices back on
–
When devices are switched back on, they are in an undefined state for a
short period. The ↑ 'Station' changes to the 'Not ready' state for this
timespan.
●
Simulation function
–
With the simulation function the 'Zone' switches from the normal operation
mode to 'Pre-ALARM' and then to 'ALARM'. The controls are activated as if
the detectors had triggered an 'ALARM'. Reset is performed by means of
the keys on the ↑ PMI.
The ↑ Control tree represents the control in the fire detection system. ↑ control
groups are grouping units for configuration and operation.
Control groups in ↑ 'Control tree'
●
'Alarming control group'
●
↑ 'Fire control group'
●
'Evac control group'
●
'Counter control group'
Each control group has one or more elements, each of which includes an input
(Cause) and an output (Effect).
●
Elements of the 'Alarming control group' are controls for internal and external
↑ alarm devices
–
Remote transmission outputs for 'Fire' and 'Fault'
–
Eight more remote transmission outputs
●
Elements of ↑ 'Fire control group' are controls for building equipment.
●
Elements of 'Evac control group' are controls for alarm and announcement
devices.
A6V10211076_i_en_--
2015-12-15