Polling / Deleting The Event Memory - Siemens FC7xx Operation Manual

Fire control panel / fire terminal
Table of Contents

Advertisement

Operation
5

Polling / Deleting the event memory

5.26 Polling / Deleting the event memory
102 | 184
Building Technologies
Fire Safety
As an alternative to the indication of the event memory on the ↑ 'Station', the data
of the event memory may also be transmitted to a PC in a standard format. To do
so, a PC with a configuration tool must be connected to the 'Station'.
You will find more information in document 'A6V10210424'.
Polling the event memory
1. Select 'Main menu' > 'Functions'.
 The 'Functions' menu is open.
2. Select 'Event memory'.
 The 'Select station' window is open.
3. Select the ↑ 'Station' you want.
 The list of all events for 'Station' is displayed.
 Using the softkeys 1-2, you can now filter by category, or date/time.
Navigating in the event memory
Entering a 3-digit number in the event memory (e.g.: 1, 132, 500) and confirming
by pressing <ok> takes you straight to the corresponding entry.
Deleting the event memory
1. Select 'Main menu' > 'Functions'.
 The 'Functions' window is open.
2. Select 'Maintenance' and confirm with <ok>.
 A list of all element categories on which a command of the 'Maintenance'
command group can be executed is indicated.
3. Select ↑ 'Station'.
 The 'Enter address' window is open.
4. Enter the number of the 'Station' on which you want to delete the event
memory and confirm with <ok>.
 The 'Select command' window is open.
5. Select the 'Delete event memory' command and confirm with <ok>.
 The event memory of the selected 'Station' is deleted.
A6V10211076_i_en_--
2015-12-15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ft724

Table of Contents