System description
9
Control
9.5.5.1 Damper control states and message texts on the display
Control state
Active
Transition from active >
inactive
Inactive
Transition from inactive >
active
Active or inactive
156 | 184
Building Technologies
Fire Safety
When the damper control is activated/deactivated, the operating states of the
damper actuators are shown on the display. This makes it possible to analyze any
faults that occur while the actuator is opening or closing.
The damper control state and the display of this state on the PMI are dependent
on the limit value for open or closed dampers OR on the state of the 'Main
damper'.
Fire damper control
Message text on the display
Damp.ct1 Closed/confirmed
Damper 1/1 Closed/confirmed
Damper 1/3 Closed/confirmed
Damp.ct1 Closed/confirmed
Damper 1/1 Closed/confirmed
Damper 1/3 NOT closed
Damp.ct1 Closed/confirmed
Damper 1/1 Closed/confirmed
Damper 1/3 Open/unexpected
Opening..
No message
Damp.ct1 NOT open
Damper 1/3 NOT open
Damp.ct1 NOT open
Damper 1/3 Closed/unexpected
Closing..
Position undefined
Operating state of the fire damper
actuator
Closed
Not fully closed
Actuator not moving; mechanical
problem
Open line
Transition from closed > open
Damper opening
Open
Not fully open
Actuator not moving; mechanical
problem
Open line
Thermostat active or in test mode
Transition from open > closed
Damper closing
Both actuator switches are closed due
to a fault
A6V10211076_i_en_--
2015-12-15