9.3 Acquisition
Danger level
Addressed detector line
Automatic
0
No danger
1
Possible danger Button not
2
Probable
danger
3
Highly probable
danger
Building Technologies
Fire Safety
The detectors detect the fire phenomena, e.g., smoke, heat, or carbon monoxide,
and transmit the ↑ danger level to the 'Zone'.
Figure 17: Information flow of the ↑ danger levels
D
↑ 'Detection tree'
a
Detector / channel
b
'Zone'
0...3 Danger levels
Overview of ↑ danger levels, divided according to line type and
detector type
↑ Collective detector line Technical input
Manual
No danger
No danger
↑ Detector line resetting
pressed
–
Alarm verification of the
first alarm is running
Button
Highly probable danger
pressed,
danger
Table 8: Danger levels
System description
Acquisition
No danger (entry contact opened)
–
Danger
●
Input contact closed
●
Input configured as not
relevant for degraded mode
Danger
●
Input contact closed
●
Input configured as not
relevant for degraded mode
A6V10211076_i_en_--
9
143 | 184
2015-12-15