System description
9
Alarm verification concept (AVC)
1
mx
2
t1..
GA
1
Alarm event
2
Local alarming
3
Manual call point or <Alarm delay off> on
'Station'
mx
'Unmanned operation' operation mode
m
'Manned operation' operation mode
t1..
Time t1 for attendance check
..t1 X Time t1 has expired
160 | 184
Building Technologies
Fire Safety
m
q
t2..
qx
..t1 X
Figure 26: Alarm verification
?
3
q
Acknowledge at ↑ 'Station'
qx
Not acknowledged
t2..
Time t2 to investigate the source of alarm / the
fire location
..t2 X
Time t2 has expired
r
Reset on 'Station'
rx
Not reset
GA
↑ Global alarming
r
rx
..t2 X
A6V10211076_i_en_--
2015-12-15