Operation
5
ALARM Procedure
5 Operation
5.1 ALARM Procedure
1
<Acknowledge>
2
Top line on the display
3
<Softkey 2> 'Show intervention text' if displayed
4
Indication of the fire location on the display
40 | 184
Building Technologies
Fire Safety
In this part of the document you will find brief descriptions and detailed operation
sequences for important functions of the fire detection installation. In addition, you
can find your preferred procedures in the representation of exemplary operation
sequences.
Certain commands on the fire control panel can only be executed by the service
technician or someone with access level 3. You will find a description of these
specific commands in document A6V10210416. See chapter 'Applicable
documents'.
System without delayed alarm transmission (AVC)
If your fire detection system has no delayed alarm transmission function ('AVC),
the variant 'Fire Brigade in' 'mm:ss' in Step 2 (see below) does not apply.
5
<Alarm device>
A
<Alarm delay off>
R
<Reset>
A6V10211076_i_en_--
2015-12-15