Control Test - Siemens FC7xx Operation Manual

Fire control panel / fire terminal
Table of Contents

Advertisement

Operation
5
Testing

5.12.4 Control test

76 | 184
Building Technologies
Fire Safety
The 'Control test' checks the function of configured controls.
During the 'Control test', the controls function in the same way as during normal
operation; however, the hardware is not actuated.
The ↑ effects of the controls, e.g., the actuation of digital outputs and the sounders
or the execution of commands is ensured, but the respective hardware receives no
signal and is thus not activated.
All controls can be set to 'Control test'.
Testing a control
1. Select 'Main menu' > 'Functions'.
 The 'Functions' window is open.
2. Select 'Test'.
 A list of all element categories on which a command of the 'Test' command
group can be executed is indicated.
3. Select the ↑ 'Fire control group' element category.
 The 'Enter address' window is open.
4. Press <ok> without entering an address.
 A list of all 'Fire control groups' is displayed.
5. Select the desired 'Fire control group' and press <softkey 1>.
 The 'Select command' window is open.
6. Select 'Control test'.
 The control test is performed.
Example of selecting commands for the 'Control test' in the 'Fire
control group' element category:
Selecting element category
↑ Section
Zone
Sounder
RT control
Fire control group
Select command
Control test END
Control test
(2)
(3)
(4)
(5)
(6)
(1)
(2)
A6V10211076_i_en_--
2015-12-15