Siemens FC7xx Operation Manual page 43

Fire control panel / fire terminal
Table of Contents

Advertisement

Step
Action / Condition
1
Press <Acknowledge> on the Person
Machine Interface
2
Read top line on display
'Fire Brigade requested'
'Fire Brigade in' 'mm:ss'
'Call Fire Brigade !' if:
Remote transmission switched off
Remote transmission blocked or
defective
No remote transmission available
3
Only with PIN for the 2,2 access level:
Press <Softkey 2> 'Show intervention text'
or press <Show intervention text> button
Press <Jump back>
4
Read off fire location on display
5
If alarm devices are activated:
Press <Silence Alarm> on the Person
Machine Interface
6
Go to the fire location
7
Decide: MAJOR INCIDENT or ↑ minor
incident
Condition
Fire brigade has been called
'Fire Brigade in' 'mm:ss'
Countdown is running
'Call Fire Brigade !'
No automatic transmission to
the fire brigade
Building Technologies
Fire Safety
Procedure in the event of alarm
Procedure in the event of a major incident or minor incident
MAJOR INCIDENT
Save people
Guide the fire brigade to the fire
location
Fight the fire
Trigger the manual call point
immediately
or
Press <Alarm delay off>
Call the fire brigade on the phone!
Before resetting, the acoustic alarm devices must be deactivated. See Step 5.
1
Reset
It may be necessary to air the room before 'Reset' is possible.
You can temporarily ↑ switch off elements that cannot be reset.
ALARM procedure PMI with FBP [AU]
Consequence / Status
⇨ With 'AVC, countdown t2 for examining the cause
of 'ALARM' starts
⇨ 'ALARM' is transmitted to the fire brigade
⇨ 'ALARM' is transmitted to fire brigade in mm:ss
Remaining time is shown as Countdown
⇨ Fire brigade must be called by phone!
⇨ No automatic transmission to fire brigade
⇨ Intervention text is displayed
⇨ Fire location is displayed
⇨ Deactivates the acoustic alarm devices
Minor incident
Try to prevent fire brigade
deployment
Press <Reset>
Press <Reset>
Operation
5
1
1
43 | 184
A6V10211076_i_en_--
2015-12-15