Mitsubishi Electric MELSEC FX3U Programming Manual page 68

Melsec fx series programmable logic controllers
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
3. Click [Individual setting] button to display "Positioning instruction settings" dialog box.
In this dialog box, set the positioning table for each pulse output destination.
Set item
Y0
Y1
*1
Y2
*2
Y3
Rotation direction signal
Head Address
No.
Positioning Instruction
Pulse
Frequency [Hz]
Up
Down
Insert
Delete
Delete all lines
66
Contents of setting
Set the positioning table for the pulse output destination Y000.
Set the positioning table for the pulse output destination Y001.
Set the positioning table for the pulse output destination Y002.
Set the positioning table for the pulse output destination Y003.
Set the relay number of the rotation direction output signal.
Initial setting: Pulse output destination Y000: Y010
Pulse output destination Y001: Y011
Pulse output destination Y002
Pulse output destination Y003
→Refer to the Positioning Control Manual.
Set the head number of devices storing the set data (pulse number and
frequency).
1600 devices (FX
and FX
3U
3UC
starting from the head device number set here without regard to the
number of axes.
Initial setting: R0
→Refer to the Positioning Control Manual.
This column shows the table number.
Numbers 1 to 100 can be set.
Select the positioning type among the following:
DDVIT (Interrupt positioning instruction)
DPLSV (Variable speed output pulse instruction)
DDRVI (Relative positioning instruction)
DDRVA (Absolute positioning instruction)
→Refer to the Positioning Control Manual.
Set the pulse number output by the operation (instruction) set in
"Positioning Instruction" column.
→Refer to the Positioning Control Manual.
Set the speed (pulse frequency) output by the operation (instruction) set
in "Positioning Instruction" column.
→Refer to the Positioning Control Manual.
This button transposes the selected line to the upper line.
This button transposes the selected line to the lower line.
This button inserts a line in the currently selected position.
This button deletes the currently selected line.
This button deletes the entire setting of the positioning table for the
selected pulse output destination.
2 Overview (Sequence Program)
2.7 Types and Setting of Parameters
This example shows a window
in an FX
*1
: Y012
*2
: Y013
) or 1200 devices (FX
) are occupied
3G
*3
/FX
PLC.
3U
3UC
Setting range
FX
/FX
:
3U
3UC
Y000 to Y357
M0 to M7679
S0 to S4095
FX
:
3G
Y000 to Y177
M0 to M7679
S0 to S4095
FX
/FX
:
3U
3UC
D0 to D6400
R0 to R31168
FX
:
3G
D0 to D6400
R0 to R22800
Refer to the
Positioning Control
Manual.
Refer to the
Positioning Control
Manual.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec fx3ucMelsec fx3g

Table of Contents