Mitsubishi Electric MELSEC FX3U Programming Manual page 103

Melsec fx series programmable logic controllers
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Off-delay timer and one-shot timer
X000
X000
M0
M1
10
M2
sec
M3
Flicker timer
X000
M 3
X000
M 2
M 1
In addition, the timer time can be set according to the switch input time by the teaching timer instruction
TTMR (FNC 64).
S
m
FNC 65
T 10
K100
STMR
10
10
sec
sec
10
10
sec
sec
FNC 65
T 10
K100
STMR
D
A value specified by "m" becomes the set value
M0
of the timer specified by
example.
M0 is an off-delay timer.
M1 is a one-shot timer after "ON → OFF"
operation.
M2 and M3 are provided for a flicker timer, and
connected as shown in the program example for
flicker timer (below).
When M3 is connected as shown in the left
M0
figure, M2 and M1 become flicker outputs.
When X000 is set to OFF, M0, M1 and M3 are
turned OFF and T10 is reset after the set time.
Do not use the timers here in other general
circuits again.
4 Devices in Detail
4.5 Timer [T]
S
. 10-second in this
101
1
2
3
4
5
6
7
8
9
10