38.3.2 Operations of special devices for error detection

Special auxiliary relays for error detection and special data registers for error detection operate in the
relationship shown below.
The state of error occurrence can be checked by monitoring the contents of auxiliary relays and data registers
or by using the PLC diagnosis function programming tool.
By using the PLC diagnosis function provided in the programming tool (GX Developer), Graphic
Operation Terminal (GOT 1000) or the display module (FX
(D8060 to D8067, D8438, D8449) can be checked in message format.
D8009
M8009 24V DC down
D8060
M8060 I/O configuration error
D8061
M8061 PLC hardware error
M8069
I/O
D8062
M8062 Serial communication error 0
bus check
D8063
M8063 Serial communication error 1
D8438
M8438 Serial communication error 2
D8064
M8064 Parameter error
D8065
M8065 Syntax error
D8066
M8066 Circuit error
D8067
M8067 Operation error
After clearing errors, forcibly clear M8068 using the device monitor function in a programming tool.
M8316
M8318
D8449
M8449

38.3.3 Error detection timing

Error item
M8060 I/O configuration error
M8061 PLC hardware error
M8062 Serial communication error 0 [ch 0]
M8063 Serial communication error 1 [ch 1]
M8438 Serial communication error 2 [ch 2]
M8064 Parameter error
M8065 Syntax error
M8066 Circuit error
M8067 Operation error
M8068 Operation error latch
M8109 I/O refresh error
M8316 Unconnected I/O designation error
M8318 BFM initialization failure
M8449 Special block error
M8068 Operation error latch
Unconnected I/O
designation error
BFM initialization failure
Special block error
ERROR LED
PLC
status
status
Unlit
RUN
Lit
STOP
Unlit
RUN
Unlit
RUN
Unlit
RUN
Flickering
STOP
Flickering
STOP
Flickering
STOP
Unlit
RUN
Unlit
RUN
Unlit
RUN
Unlit
RUN
Unlit
RUN
Unlit
RUN
38 Error Check Method and Error Code List
38.3 Supplementary Explanation of Devices for Error Detection
-7DM), the contents of the error code
3U
D8004
M8004
Special M number
ON when an error
(smallest device
occurs
number) of error
occurrence
32K Error step number
D8315
D8314
The error step number is also stored in
D8069, but only for programs 32K
steps and less.
1st error step latched
D8313
D8312
The error step number is also stored in
D8068, but only for programs 32K
steps and less.
Error step number
D8317
D8316
Error unit number
D8318
Error BFM number
D8319
Error detection timing
When power
When PLC mode
is turned from
switches from
OFF to ON
STOP to RUN
Check
Check
Check
Check
Check
Check
Other timing
Always
When receiving signal
from counterpart station
When receiving signal
from counterpart station
When receiving signal
from counterpart station
When program is changed
(STOP)
When program is
transferred (STOP)
RUN mode
Always
RUN mode
Always