Fnc150 - Dszr / Dog Search Zero Return - Mitsubishi Electric MELSEC FX3U Programming Manual

Melsec fx series programmable logic controllers
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
20.1
FNC150 – DSZR / Dog Search Zero Return
Outline
This instruction executes a zero return, and aligns the mechanical position with a present value register inside
the PLC.
In addition, this instruction enables the following functions not supported by the ZRN (FNC156) instruction:
• DOG search function
• Zero return by the near-point (dog) signal and zero-phase signal
It is not possible, however, to count the zero-phase signal and then determine the zero point.
1. Instruction format
FNC 150
DSZR
2. Set data
Operand type
S
1
S
2
D
1
D
2
3. Applicable devices
Bit Devices
Oper-
and
System User
Type
X Y M T C S D .b KnX KnY KnM KnS T C D R U \G
S
1
S
2
2
D
1
3
D
2
4
1 : "D .b" is available only in FX
available.
2 : Specify X000 to X007.
3 : Specify Y000, Y001 or Y002
*3
Y003
from a high-speed output special adapter
*1.
Y002 is not available in 14-point and 24-point type FX
*2.
High-speed output special adapters can be connected only to FX
*3.
To use Y002 and Y003 with a high-speed output special adapter, connected a second high-
speed output special adapter.
Points
• When using a relay output type FX
• Outputs of special high speed output adapters work as differential line drivers.
572
→ For explanation of the instruction, refer to the Positioning Control Edition manual.
Mnemonic
16-bit Instruction
9 steps DSZR
Device number for near-point signal (dog)
Input number for zero-phase signal
Device number (Y) from which pulses are to be output
Device number to which rotation direction signal is output
Digit Specification
1
1
and FX
3U
*1
transistor output from the main unit, or specify Y000, Y001, Y002
20 Positioning Control – FNC150 to FNC159
20.1 FNC150 – DSZR / Dog Search Zero Return
→ For cautions on using special high speed output adapters,
refer to the Positioning Control Edition manual.
Operation Condition
32-bit Instruction
Continuous
Operation
Description
Word Devices
Special
System User
Unit
PLCs. However, index modifiers (V and Z) are not
3UC
*2
.
3G
PLC, a special high speed output adapter is required.
3U
Mnemonic
Operation Condition
Others
Con-
Real
Index
stant
Number
V Z Modify K H
E
PLC.
PLC.
3U
Data type
Bit
Charac-
Pointer
ter String
" "
P
*3
or