13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup
Outline
This pulse output instruction has the acceleration/deceleration function.
1. Instruction format
FNC 59
D
PLSR
2. Set data
Operand Type
S
1
S
2
S
3
D
3. Applicable devices
Bit Devices
Oper-
and
System User
Type
X
Y
M T C S D .b KnX KnY KnM KnS T C D R U \G
S
1
S
2
S
3
1
D
1: Specify a transistor output on the main unit or Y000 or Y001 on a special high speed output adapter
2: This function is supported only in FX
*1. High-speed output special adapters can be connected only to FX
Explanation of function and operation
1. 16-bit operation (PLSR)
Pulses are output from output (Y)
maximum frequency
Command
input
FNC 59
PLSR
: Maximum frequency (Hz)
S
1
Allowable setting range: 10 to 32767 (Hz)
: Total number of output pulses (PLS)
S
2
Allowable setting range
FX
3G
FX
/X
3U
3UC
: Acceleration/deceleration time (ms)
S
3
Allowable setting range: 50 to 5000 (ms)
: Pulse output number
D
Allowable setting range: Y000, Y001
Mnemonic
16-bit Instruction
9 steps PLSR
Maximum frequency (Hz)
Total number of output pulses (PLS)
Acceleration/deceleration time (ms)
Device number (Y) from which pulses are to be output
Digit Specification
/FX
3U
by the specified number
D
over the time
S
S
1
S
S
S
1
2
3
Maximum
Total
Acceleration/
frequency
number
deceleration
(HZ)
of output
time
pulses
(ms)
(PLS)
: 110 to 32767(PLS)
: 1 to 32767(PLS)
13 High Speed Processing – FNC 50 to FNC 59
13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup
Operation Condition
32-bit Instruction
Continuous
17 steps DPLSR
Operation
Description
Word Devices
System
Special
User
Unit
V Z Modify
2
2
2
PLCs.
3UC
3U
S
2
(ms).
3
Pulse frequency
(Hz)
D
Output
number
(Y000,
Y001)
Acceleration/
S
3
deceleration time
Mnemonic
Operation Condition
Continuous
Operation
Data Type
16- or 32-bit binary
16- or 32-bit binary
16- or 32-bit binary
Bit
Others
Real
Charac-
Index
Constant
Number
ter String
K
H
E
" "
PLC.
with acceleration/deceleration to the
Maximum frequency
S
1
Total number of
output pulses
(PLS)
S
2
Acceleration/
S
3
deceleration time
11
12
13
14
15
Pointer
P
16
*1
.
17
18
19
20
399

Advertisement

Table of Contents
loading

This manual is also suitable for: