3. Handling of pulse output terminals in the FX
The outputs Y000 and Y001 are the high speed response type.
When using a pulse output instruction or positioning instruction, adjust the load current of the open collector
transistor output to about 10 to 100 mA (5 to 24V DC).
Item
Operating voltage range
Operating current range
Output frequency
When the load is smaller, connect a dummy resistor in parallel to the outside of a used output terminal (Y000
or Y001) as shown in the circuit diagram below so that the specified current shown above flows in the output
transistor.
Equipment
load
resistor
External
power
supply
4. Cautions on special high speed output adapters
1) Outputs of special high speed output adapters work as differential line drivers.
2) Set the pulse output type setting switch in a special high speed output adapter to the "pulse chain +
direction" (PLS DIR) side.
If the switch is set to the "forward rotation pulse chain reverse rotation pulse chain" (FP RP) side, normal
operations are disabled. The pulse output destination changes depending on the PLC output status as
shown in the table below.
Pulse output
destination
= Y000
D
= Y001
D
3) Set the pulse output type setting switch while the PLC is stopped or while the power is OFF.
Do not manipulate the pulse output type setting switch while pulses are being output.
4) When special high speed output adapters are connected, the same output numbers in the main unit are
assigned as shown in the table below.
Only wire the appropriate output terminals.
Outputs in special high speed output adapters and the main unit operate as shown below.
Assignment of output numbers in special high speed output adapter
Setting status of output
form setting switch
"FP RP" side
"PLS DIR" side
402
Description
5 to 24V DC
10 to 100 mA
100 kHz or less
Dummy
resistor
Input circuit
Output affecting
operation
While Y004 is ON, pulses are output from Y000 in the high speed output
adapter.
Y004
While Y004 is OFF, pulses are output from Y004 in the high speed output
adapter.
While Y005 is ON, pulses are output from Y001 in the high speed output
adapter.
Y005
While Y005 is OFF, pulses are output from Y005 in the high speed output
adapter.
Signal name
Forward rotation
pulse chain (FP)
Reverse rotation
pulse chain (RP)
Pulse chain
Direction
13 High Speed Processing – FNC 50 to FNC 59
13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup
, FX
and FX
3G
3U
PLC
(transistor output)
[sink output]
Y000
COM1
Setting name in each
positioning instruction
Pulse output destination
Rotation direction signal
Pulse output destination
Rotation direction signal
series main units
3UC
Operation
Output number
1st unit
1st axis 2nd axis 3rd axis 4th axis
Y000
Y001
Y002
Y004
Y005
Y006
Y000
Y001
Y002
Y004
Y005
Y006
2nd unit
Y003
Y007
Y003
Y007