Switch Specifications; 260If Module - YASKAWA MP900 Series User Manual

Hide thumbs Also See for MP900 Series:
Table of Contents

Advertisement

Basic Specifications

2.2.1 260IF Module

2.3 Switch Specifications

2
Refer to 4.1 Basic Use of the 260IF Module for setting details.
SW1
The baud rate for DeviceNet communications and Slave/Master settings are made on this
DIP switch.
Pin
Meaning
DR0
DeviceNet
baud rate
DR1
X1
Slave/Master setting
X2
Not used
SW2 and SW3
These rotary switches are used to set the DeviceNet MAC ID.
Switch
Meaning
*10 (SW2)
MAC ID 10's digit
*1 (SW3)
MAC ID 1's digit
www.dadehpardazan.ir 88594014-15
Table 2.1 SW1 Specifications
DR1
DR0
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
Slave (default)
ON
Master
Always OFF
Table 2.2 SW2 and SW3 Specifications
0 to 6
Set a two-digit local node MAC ID (0 to 63) in
decimal using two rotary switches (default: 00).
0 to 9
2-4
Setting
125 kbps (default)
250 kbps
500 kbps
(Do not change)
Setting