SPECIFICATIONS
Operate time:
Typical times are average operate times including variables such as frequency change instance, test method, and so on, and can vary by
±0.5 cycles.
TURBINE FREQUENCY OUT-OF-BAND (OOB) ACCUMULATED OPERATING TIME
Frequency OOB accumulation:
2
Frequency OOB accumulation pickup:
Frequency OOB accumulator preset:
Level accuracy:
Minimum volt/amp supervision:
Timer accuracy of accumulation:
BREAKER FAILURE
Mode:
Current supervision:
Current supv. pickup:
Current supv. dropout:
Current supv. accuracy:
0.1 to 2.0 × CT rating:
above 2 × CT rating:
Timer accuracy:
BREAKER ARCING CURRENT
Principle:
Initiation:
Compensation for auxiliary relays:
Alarm threshold:
Fault duration accuracy:
Availability:
BREAKER FLASHOVER
Operating quantity:
Pickup level voltage:
Dropout level voltage:
Pickup level current:
Dropout level current:
Level accuracy:
Pickup delay:
Timer accuracy:
Operate time:
BREAKER RESTRIKE
Principle:
Availability:
Pickup level:
Reset delay:
SYNCHROCHECK
Max voltage difference:
Max angle difference:
Max freq. difference:
Hysteresis for max. freq. diff.:
Dead source function:
S-CLS MAX dF:
S-CLS MIN dF:
2-26
typically 9.5 cycles at 2 × pickup
typically 8.5 cycles at 3 × pickup
typically 6.5 cycles at 5 × pickup
7 sets; 20 to 70 Hz in steps of 0.01
1 to 65536 s in steps of 1
1 to 65536 s in steps of 1
±0.01 Hz
0.1 to 1.25 pu of V_1 or I_1
±1% or 1 second, whichever is greater
1-pole, 3-pole
phase, neutral current
0.020 to 30.000 pu in steps of 0.001
97 to 98% of pickup
±0.75% of reading or ±2% of rated (whichever is greater)
±2.5% of reading
±3% of operate time or ±1/4 cycle (whichever is greater)
2
accumulates breaker duty (I
t) and measures fault duration
programmable per phase from any FlexLogic operand
0 to 65.535 s in steps of 0.001
2
0 to 50000 kA
-cycle in steps of 1
0.25 of a power cycle
1 per CT bank with a minimum of 2
phase current, voltage, and voltage difference
0.004 to 1.500 pu in steps of 0.001
97 to 98% of pickup
0.020 to 1.500 pu in steps of 0.001
97 to 98% of pickup
±0.5% or ±0.1% of rated, whichever is greater
0 to 65.535 s in steps of 0.001
±3% of operate time or ±42 ms, whichever is greater
<42 ms at 1.10 × pickup at 60 Hz
detection of high-frequency overcurrent condition ¼ cycle after breaker opens
one per CT/VT module (not including 8Z modules)
0.1 to 2.00 pu in steps of 0.01
0.000 to 65.535 s in steps of 0.001
0 to 400000 V in steps of 1
°
0 to 100
in steps of 1
0.00 to 2.00 Hz in steps of 0.01
0.00 to 0.10 Hz in steps of 0.01
None, LV1 & DV2, DV1 & LV2, DV1 or DV2, DV1 xor DV2, DV1 & DV2 (L = Live, D = Dead)
0.10 to 2.00 Hz in steps of 0.01
0.00 to 1.00 Hz in steps of 0.01
CHAPTER 2: PRODUCT DESCRIPTION
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL